20180612143355.pdfJune 12,2Q18 Chuck Miller, Plans Examiner City of Edmonds Re: Plan Review Gomments Plan Check: BLD2018-0363 - 2nd review Project Address: 2170176th Avenue W, Suite 304 Project: Healthcare Realty tenant improvement Scope: Remove/add non-bearing interior walls and doors to reconfigure spaces - nonseparated Business Group B occupan cy - 20 occupants - VA construction - no sprinkler system - mechanical, plumbing, fire alarm, etc. under separate permits Dear Mr. Miller, Thank you for taking the time yesterday to discuss the comments for the Healthcare Realty spec suite... .it was greatly appreciated! Please find our responses and revised sheets to address your comments. On sheet 40.41 - I.egends - Partitions, Doors & Door Schedule: 5. Partition-Type: Vertical Configuration Legend - Type 'a'- Fire-Rated Partitron b. Provide on the plans information regarding the required attacltment at the top of the partítion to the deck above. Include the specifiedfasteners and their spacing. The response to the earlier plan review comment states: "See added details on attached 40.41". The additional details - Detail 8 - Fire Rated at Head Condition - and - Designs for Fire-Rated Heads-of-V/all - reference sheet 'A0.43', UL Design HW-D0264,UL Design HW-D-0218, UL Design HV/-D- 0049, and UL Design HW-D- 0042 for further information and construction criteria. Sheet 'A0.43' and the referenced UL Designs could not be found among the resubmitted construction documents. Provide on the plans the required construction criteria of the listed f,rre-resistance rated head-of-wall assemblies. The information must include the specified components of the fire-resistance rated assembly (type and thickness of the 'forming material' - fill, void, or cavity material) and their installation criteria (compression percentage or physical attachment- application) to guide proper construction and inspection. See attached NEW sheet 40.43 On sheet A2.Il - Third Floor Plan & Ceiling Plan: 7 . Light Fixture Schedule a. Provide a lighting control narrative (typ"(t) and locations of lighting controls, suclt as occupant sensor and tíme switch, meeting WSEC C405.2) per WSEC C103.2. The response to the earlier plan review comment states: "See added notes on 42.11". The added notes - General Daylight Zone Notes - appear to be general in nature, reference daylight zones not represented on the plans, and a 425.778.1530 www.teba¡chitects.com 21911 76'h Ave w. Suite 210 Edmonds,'WA 98026 CITY COPY RESUB JUN I 2 20t8 %BPæmmrs* tgbPage I of2 .RCP' plan indicating the location of occupancy sensors that could not be found. Most of the areas do not appear to be subject to the 'daylight responsive control' requirements of V/SEC C405.2.4 due to the lack of windows or number of fixtures in the daylight zones. Typically, occupancy sensors are installed per WSEC C405.2.1. Most of the specified areas do not appear to be exempt from the 'occupancy sensor control' requirements of WSEC C405.2.I. The noted exception, WSEC C405.2.2,Item2, applies to those areas not otherwise provided with occupancy sensor controls. Unlike occupancy sensor controls, which would sense the presence of a medical providerþatient and allow the space to remain illuminated at desired/required levels, time switch (and daylight responsive (redtrction)) controls would turn off or reduce the lighting level as programmed (without regard to the use/need), justifying the exception of those controls. Time switch control(s) with a manual override should be provided for the lighting serving the following spaces:. 301 - Waiting. 302 - Reception. 3ll -Corridor See attached revised sheet A2.l I lf there are any further comments or questions regarding this project, please let me know. My number is 425-599-4463 or via email at gdais@tgbarchitects. Sincerely,tu Gina Dais Attachments: 40.43 and 42.1 1 2l9l I 7ó'h Ave W. Suire 210 Edmonds, WA 9802ó 425.778.1530 www.tpbarchitects. com tgb :; !., :j I i, ". I Page 2 o12