20180620135807.pdfDate: June 18,2018
To:Eric Carter, Plans Examiner, Building Division, City of Edmonds
eric.carter@ed mondswa.gov
From: Kelli Martin, Permit Specialist, The Permit Network
thepermitnetwork@ gmail. com
Comments Response Letter- BUILDING D¡V|S|ON REVIEW
Application #: 81D20180354
Project: James Weis- Slngle Family Residence
Project Address: 16630 74th Pl W
Re:
The purpose of this letter is to address comments received from you on May 18, 2018 regarding the
aforementioned project. For your convenience and to expedite the review and approval process, your
originalcomments are included and our responses are provided in BOLD.
The following new or revised documents are incorporated by reference herein:
r Sheet SP- Site Plan
o Sheets A1 to 410- House Plans
BUITDING DIV¡SION REVIEW
Plan A3
1. The plans indicate the wine cellar as "unheated" space. The proposed door to the wine cellar
must comply with Washington State Ënergy Code R 402.2.4. Please add the applicable notes to
the plans.
Respondent: Doug Williams- Doug Williams Design
Response: note added to both doors (and cloudedf on Sheet A3, lndicating 20 min rated, self-
closing doors for both wine cellar and shop.
2. lt is unclear if the proposed shop will be "conditioned" spâce. lf this space is to be conditioned,
please note on the plans. lf the space is not to be conditioned, the doors leading to the
conditioned space will be required to comply with R 402.2.4 as mentloned in item 1..
Respondent: Doug Williams Design
Response: note added to both doors (and clouded) on Sheet 43, indicating 20 min rated, self-
closing doors for both wine cellar and shop.
3. Bearn 5 and 6 supporting the deck joist exceed to allowable deflection limits. Please clarify and
change the beam size of pier spacirtg on the plans.
Respondent: Doug Williams Deslgn
Response: Beam 5 & 6 upgraded one size to L3W and clouded on sheet 43, Beam 4 upgraded to
tl% as well for aesthBtic consistency.
RESU.'B
JUN 2 0 zt't$
I
BIJLDINGDEPAFITMENTCIÎYC)FEDMOI\Ð6
crïY c0PY
4. The 2x10 Ht #2 PT joist that are supported by beam 5 are over spanned for the proposed
conditions. When sizing your framing members, be sure to use both the incising and wet service
factors in addition to the minimum of 60PSF of live loading as required in table R301.5.
Respondent: Doug Wllliams Design
Response: All deck joists upgraded toZxl.2 and clouded on A3,
Plan A4
S. The plans indicate gas fireplaces to be located in bedrooms 2 and 3 as well as the master suite.
IRC 315.3 require a carbon monoxide detector to be installed within each bedroom with a fuel
burning appliance. Please add the required detectors to the plans.
Respondent: Doug Williarns- Þoug Williams Design
Response: Carbon Monoxide detectors added for all (4) first floor Gas Fireplaces and clouded on
sheet 44.
lf you have questions or need additional informatien, please callor e-mail me at
thepermitnetwork@ gmail.com
Resp
f/4¿rLâ"^
Kelli Martin, Permit Specialist