20180809123921.pdfffi JACKSON I MAIN LARCHITECTURE August 8,20L8 Chuck Miller Senior Plans Examiner 121 5th Ave N Edmonds, WA 98020 RE: Plan Check: BLD20L8-0864 - 1st review Anytime Fitness Tenant lmprovement - Change of Use 22824 100th Avenue W Edmonds, WA 98020 Dear Chuck: The following are Jackson I Main Architecture (JMA) responses to the correction letter, dated July 31, 2018. Responses are numbered to correspond with the order in which the questions were received for the project referenced above: General plan review note - Per lnternational Building Code (lBC) 903.2.13, as amended by the Edmonds Community Development Code (ECDC) 19.25.035.A.4, an existing building having a fire area of 5,000 or greater square feet separated from the remainder with existing fire barriers that undergoes alterations and/or a change of occupancy must have an approved automat¡c fire sprinkler system installed and maintained. Those port¡ons separated from the area undergoing the alterations, repairs, or changes of occupancy as noted above shall be required to comply with ECDC 19.25.035.4.5. For the purposes of ECDC 19.25.035, spaces may not be separated by adding fire barriers per IBC 707.3.tO to avoid the requirement. Assemblies shall still be provided where required by other sections of the code. Partial area automatic sprinkler systems are prohibited except where approved by the fire code official. Response: On Sheet 40.0 under Separate Submittals, the following have been added: Mechanical, Electrical, Plumbing, Fire Protection: Fire Sprinkler and Fire Alarm. On sheet 40.0 - Cover Sheet: L. Code Data a. Applicable Codes - Change on the plans the adopted code regulating plumbing systems from 'lnternational Plumbing Code'to 'Uniform Plumbing Code' per Washington Administrative Code (WAC) 51-56. Response: On Sheet 40.0 under Applicable Codes 'lnternational Plumbing Code' has been changed to 'U niform Plumbing Code.' b. Site and Building lnfo - Building Statistics - Change on the plans the 'existing occupancy type' from 'General Retail' to 'Mercantile Group M' per lnternational Building Code (lBC) 309.1. RESUB JACKSON I MAIN ARCHTTECTURE, p.S. 311 FTRST AVENUE SOUTH, SEATTLE, WA 98104 206.324.4800 dtrtSlNUtWÄArME¡{'r CXTYOF EDil,lONflS ffi JACKSON I MAIN 2ARCHTECTURE Response: On Sheet 40.0 under Site and Building lnfo - Building Statistics - the existing occupancy type has been changed from 'General Retail'to 'Mercantile (M)'- ¡t has also been changed in the Project Scope. c. Chapter 10: General Means of Egress - Occ. Load Factor i. Guest Lobby - Change on the plans the occupant load factor from 'LOOf occ.'to '15/occ.' to reflect that applied to waiting areas with casually spaced (unconcentrated) chairs per IBC Table 1004.1.2. Response: On Sheet 40.0 under General Means of Egress - Occ. Load Factor of the Guest Lobby has been updated to be l,5locc. and the occupant number is now 14. lt has been updated on the Code Compliance Plan as well. ¡i. Member Area - Change on the plans the occupant load factor from 'SOf occ.' to 'L8 inchesf occ.'to reflect that required for the represented bench seating per IBC tOO4.4. Response: On Sheet A0.0 under General Means of Egress - Occ. Load Factor of the Member Area has been updated to be t8"locc. and the occupant number is now 5. lt has been updated on the Code Compliance Plan as well. iii. Utility - Change on the plans the occupant load factor from 'L00/occ.' to '300/occ.'to reflect that applied to accessory storage areas per IBC Table 1004.1.2. Response: On Sheet A0.0 under General Means of Egress - Occ. Load Factor of all of the Exercise Area has been combined and updated to be 50/occ. and the occupant number is now 86. lt has been updated on the Code Compliance Plan as well. iv. Men's Restrooms, Women's Restrooms, and Hall- Clarify on the plans the designation of 'Accessory Use' and lack of an occupant load factor applied to those areas. They do not appear to reflect that determined using the 'function of area' criteria when calculating occupant loads using 'net' and 'gross' floor areas per IBC 1004. All occupiable spaces (even mechanicalequipment rooms) must be accounted for, including restrooms and corridors. Typically, service areas are accounted for using the 'business' function of space with a corresponding occupant load factor of '100 gross'. Response: On Sheet 40.0 under General Means of Egress - Occ. Load Factor of all the restrooms and hallway has been updated to be "business" with 100/occ. and the occupant number is now 4. lt has been updated on the Code Compliance Plan as well. Update on the plans the 'Total Occupant Load', the applicable 'Exit Requirements', and 'Minimum Number of Required Plumbing Facilities' using the occupant load determined in response to the above plan review comments. Response: On Sheet A0.0 under Exit Requirements and Minimum Number of Required Plumbing Facilities - the following has been updated to reflect the new occupant load number: Occ. load (112), Required Door Width (22.4"1, Exit Access Travel Distance (250 Feet w/Sprinkler System), Proposed Door Width lL44"l and number of Men and Women split count (112 (Men: 56 - Women 56). The info has been updated on the Code Compliance Plan as well. JAcKsoN I MAIN ARcHlrEcruRE, p.s. 311 FtRsr AVENUE sourH, SEATTLE, wA 98104 206.324.4900 JACKsoNMAtN.coM ffi JACKSON I MAIN ARCHITECTURE d. Location Map - Change on the plans the location of the proposed work identified by the 'leader line' from LOLLT Edmonds Way - Seattle Goodwill - to the west-most portion of the adjacent structure formerly occupied by Westgate Clothing Outlet. Response: On Sheet A0.0 under Location Map the leader line has been updated to reflect the proposed work site location. e. Key Plan - Change on the plans the location of the proposed work identified by the 'leader line' from IOLLT Edmonds Way - Seattle Goodwill - to the west-most portion of the adjacent structure formerly occupied by Westgate Clothing Outlet. Response: On Sheet 40.0 under Key Plan the leader line has been updated to reflect the proposed work site location. On sheet 40.1 - lnterior Accessibility: 2. A.D.A.A.G.lnteriorAccessibilityComponents a. Reach Ranges, Controls, & Operating Mechanisms - High and Low Side Reach Limits - Change on the plans the indicated 'low side reach limit' in inches from '9' to '15' per 20L0 Standards for Accessible Design Section 308.3.L. Response: On Sheet A0.1 under Reach Ranges, Controls & Operating Mechanisms - High and Low Side Reach Limits the low side reach limit has been changed from 9" to 15" b. Foodservice Lines, Tableware Areas, & Checkout Aisles - Tableware Areas - Change on the plans the indicated maximum height above the finish floor in inches for an obstructed high side reach from '54' to'46' per 2010 Standards for Accessible Design Section 905.4.1. Response: On Sheet A0.1 Foodservice lines, Tableware Areas, and Checkout Aisles - tableware areas - has been removed from the sheet - as it does not pertain to our scope of work. The removal has been clouded. General note regarding the above plan review comments - ln addition to the changes above, the placement of the numbering does not appear to correspond with many of the separate requirements. Response: On Sheet A0.1 the sections of the 2OOg l.C.C.lANSl A117.1 that are referenced in the notes have been updated to reflect the accurate sections. The notes are clouded on the sheet that have been modified. 3. 2OO9 |.C.C./A.N.S.|. ALL7.L a. Doors - Provide on the plans a detail representing the requirements for two doors in a series, such as that represented serving spaces 'L09' and '110', per ICC 4117.1-2009 Section 4O4.2.5. Response: On Sheet 40.1 under doors, the two doors in a series that is represented serving spaces 109 and 110 has been updated to reflect a 60" minimum clear space. JACKSON I MA|N ARCHTTECTURE, p.S. 311 F|RST AVENUE SOUTH, SEATTLE, WA 98104 206.324.4800 JACKSONMAIN.COM ffi/â:$?Il yflT 4 b. Restrooms - Parallel Approach - Eliminate from the plans the provided detail regarding a 'parallel approach' to drinking fountains. The allowance is only for drinking fountains primarily for children's use per ICC 4117.1-2009 Sectio n 6O2.2. Response: On Sheet 40.1 under Restrooms - ParallelApproach, the parallel approach has been removed. The removal has been clouded. c. Foodservice Lines, Tableware Areas, & Checkout Aisles i. Obstructed Forward Reach 1. Change on the plans the label of the detail to 'Unobstructed Forward Reach'to correspond with that depicted. Response: On Sheet A0.1 under now called 'Reach Ranges'-'Obstructed Forward Reach' has been changed to'Unobstructed Forward Reach.' 2. Change on the plans the indicated 'high forward reach limit' in inches from'44' lo'48' per ICC ALI7.L-20O9 Section 308.2.L. Response: On Sheet A0.1 under now called 'Reach Ranges'- the 'High Forward Reach Limit' has been changed from 44" to 48" max. ii. Obstructed High Forward Reach -Change on the plans the indicated maximum 'forward reach depth' in inches from '23' Ìo'25' per ICC ALLT .7-2OO9 Section 308.2.2. Response: On Sheet A0.1 under now called 'Reach Ranges'- 'Obstructed High Forward Reach'- the forward reach depth has been changed 1rom20"-23" 1o20"-25," On sheet A1.0 - Demolition Plan: 4. Demolition Notes a. Note 8 - lndicate on the plans those fire-resistance rated items required to be maintained to guide proper demolition. Response: On Sheet 41.0 Mark 23 in the demolition plan legend has referenced note 8 and has been placed on the plans where it is applicable. b. Note 15 - Add on the plans the required approval from a building official for repairs, alterations, and/or changes to any structural elements. Response: On Sheet A1.0 Mark 24 in the demolition plan legend notes "approval required from a building official for repairs, alterations, and/or changes to any structural elements" and has been placed on the plans where it is applicable. On sheet 42.0 - Floor Plan Floor Plan a. lndicate on the plans the type of fixtures/furnishings to be placed in the 'Guest Lobby' and whether they are to be 'fixed/built-in' or not. Of particular concern are those furnishings required to be accessible and areas where the type of seating is used to determine an 'occupant load' per IBC Table 1004.1.2. 5 JACKSON I MAIN ARCHITECTURE, P.S. 311 FTRST AVENUE SOUTH, SEATTLE, WA 98104 206.324.4800 JACKSONMATN.COM It JACKSON I MAIN 5A.RCHITECTURE Response: On Sheet A2.0 the plan has been updated to reflect the furniture being placed in the 'Guest Lobby.' Mark 20 in the Floor Plan Legend notes there will be two free standing chairs, with the dimensions 31"W x34"D x 18" Seat Height. No other furniture will be in that space and the chairs will not affect the accessible route. b. Clarify on the plans the represented placement of the water heater serving the lavatories in spaces 'LO6' , 'LO7' ,'109', and '110'. lt does not appear to meet the maximum piping length per Washington State Energy Code (WSEC)Table C4O4.3.L. Utilization of an instantaneous water heater for each of the lavatories is typically proposed to avoid having to install a tank-type water heater in the same space and still meet the accessibility requirements of ICC 4117.1-2009. Response: On Sheet A6.0 detail 2 Enlarged Restroom Plan- A note has been added that states: "Recirculating Loop to be Located within 2'-O" of Restroom Faucet, typ." 6. Floor Plan Legend - 'Mark' L3 - Change on the plans the detail reference regarding the typical blocking for the TV from '7/A7.2' to'74/A7.2' Response: On Sheet A2.0 -Floor Plan legend Mark 13 has been updated to reflect the correct detail of L41A7.2. On sheet 43.0 - Ceiling Plan: 7. Ceiling Plan a. lndicate on the plans those spaces required to have occupancy sensor lighting controls installed per WSEC C405.2.1. Response: On Sheet 43.0 - Energy Code Requirement notes have been added; Also Mark 10 under the Plan Legend states: lnstall Occupancy Sensor Control per WSEC C405.2.1. Mark 10 has been added to the fof lowing rooms on the Ceiling Plan: All Restrooms lLO6, LO7,109, 1101, Storage/Utility Room (108), Trainer Office (104), and Office (102). b. lndicate on the plans those spaces required to have time switch lighting controls installed per WSEC C4O5.2.L. Response: On Sheet 43.0 - Energy Code Requirement notes have been added; Also Mark 11 under the Plan Legend states: lnstall Time Switch tighting Control Per WSEC C4O5.2.2. Mark 11 has been added to the Ceiling Plan to control the rest of the spaces that do not have occupancy sensors. On sheet 45.0 - Schedules: 8. Door & Hardware Schedule - Window Frames -'Mark' 'W2' - Clarify on the plans the difference in the indicated distance above the finish floor for the installation of the window and of that likely with the placement of the acoustical ceiling tile ceiling system at the height specified on sheet '43.0'- Ceiling Plan. Response: On Sheet 45.0 - Window mark 'W2'- the distance above finish floor has been updated and does not interfere with the ceiling height that is noted on the Sheet A3.0 Ceiling Plan. 9. Architectural General Notes - Note 12 - Change on the plans the wording of the readily JACKSON I MA|N ARCHTTECTURE, p.S. 311 F|RST AVENUE SOUTH, SEATTLE, WA 98104 206.324.4800 JACKSONMAIN.COM ffi JACKSON I MAIN 6ARCHITECTURE visible sign adjacent to the main doorway from "This door to rema¡n unlocked during business hours" to "This door to remain unlocked when building is occupied" per IBC L010.1.9.3, ltem 2.2. Response: On Sheet A5.0- Under Architectural General Notes - Note 12 has been updated to say "This door to remain unlocked when building is occupied" On sheet 46.0 - lnterior Elevations: 10. Plan/Elevation Legend a. 'Mark' '2' - Change on the plans the detail reference regarding the coved ceramic base lrom' 5/ A7 .!' to'2f A7 .t' Response: On Sheet A6.0 - Mark 2 has been updated to reference the correct detail numb er - 2l A7 .1. b. Add to the plans the information regarding the items 'marked' 'L7'on the various elevations, Response: On Sheet A6.0 - Mark 17 has been added to the Plan/ Elevation Legend to provide further info for the Plans and elevations on this sheet. LI Plan 1/46.0 - Enlarged Restroom Plan a. Change on the plans the following elevation 'callouts' in space 't1g' - W. Restroom: . From 'A'to'C' . From 'B'to'A' . From 'C'to'D' . From 'D'to'B' Response: On Sheet 46.0 - The following elevation callouts have been updated for space 109 - W.Restroom: 'Æ to 'C', 'B'to'Æ,'C'to'D', 'D'to'B' b. Change on the plans the following elevation 'callouts' in space 'LL}' - M. Restroom: . From 'B'to'C' . From 'C'to'B' Response: On Sheet 46.0 - The following elevation callouts have been updated for space 110 - M.Restroom: 'B' to 'C','C' to'B' t2 Plan2/A6.0 - Enlarged Restroom Plan - Change on the plans the 'marks' of the following items: ' From '10' lo'L2' ' From '12' lo'LO' Response: On Sheet A6.0 - The following 'marks' have been updated on the Enlarged Restroom Plan: '10' to'L2','L2' to'tO' 13 Elevation 4/A6.0 - Men's Shower Room Elevations - Clarify on the plans the provided depictions of the following elevation 'callouts': , rB, . rc, They do not appear to correspond with that represented on plan '1/46.0' - Enlarged Restroom Plan. JACKSON I MA|N ARCHITECTURE, P.S. 311 FIRST AVENUE SOUTH, SEATTLE, WA 98104 206324.4800 JACKSONMATN.COM Iiliâ?$9)'J yftT 7 Response: On Sheet A6.0- Men's Shower Room Elevations - The following elevations have been updated to reflect what is shown in the Enlarged Restroom Plan 1/A6.0: Elevation 'B' and Elevation'C' t4.Elevation 5/A6.0 - Women's Shower Room Elevations - Clarify on the plans the provided depictions of the following elevation 'callouts': ''c' ,,D' They do not appear to correspond with that represented on plan '1/46.0'- Enlarged Restroom Plan. Response: On Sheet 46.0 - Women's Shower Room Elevations - The following elevations have been updated to reflect what is shown in the Enlarged Restroom Plan 1/A6.0: Elevation 'C'and Elevation'D' On the provided Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all Rl: 15. lnterior Lighting - Space-By-Space Method - LTG-INT-SPACE checklist - Proposed Lighting Wattage table - Clarify the indicated watts/fixture for the proposed 'Cooper Track' in the following spaces: ''t0L'- Guest Lobby ''L03'- Member Lobby ' '105' - Stretch Area It does not appear to comply with that specified in 'Note 7' of the form. Resubmit the 'LTG-INT-SPACE' checklist as required to verify compliance of the proposed 'lnterior Lighting Power Allowance' in the response to the plan review comment. Response: On LTG-INT-SPACE Checklist - Proposed tighting Wattage table - The wattage for the proposed Cooper Track has been updated from 9 Watts to 50 Watts. This change made the space non- compliant. On sheet A3.0, Ceiling Plan - I have removed one 8' Cree LED Strip Luminaire w/hangers LS8-80I40K-89W from the space 114 and another from space 112 making the number of fixtures 25 instead of 27. This modificat¡on has made the space compliant. The changes are clouded on the ceiling plan on A3.0. Sincerely, ?hr^^^, ú^-,^ril Theresa Barnett lnterior Designer JACKSON I MAtN ARCHTTECTURE, p.S. 311 FTRST AVENUE SOUTH, SEATTLE, WA 98104 206.324,4800 JACKSONMAIN.COM