20180809140205.pdfPLAI\COMMENTS G (42s\771-0220 DATE: July 17,2018 Fosmore Construction Waldo Fosmore FROM: Eric Carter, Plans Examiner Plan Check: BLD201 8-0598 Project Address: 831 Caspers ST *.' Scope: Addition, SFR, VB Construction, Plumbing aqd Mechanical included. Please be advised that the building plans for the above referenced project have been disapproved for the pu{poses of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. Items thøt recur on lhís líst appear in itølícs. A complete review cannot be performed until the revised plans/documents. including a written response in itemized letter format indicatins where the 'clouded' or otherrvise hiehlishted chanses can be found on the revised planso have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. During the cursory review the following items were noted. General: 1. RECONCILED The City of Edmonds requires plans with load carrying members 8' and longer to"have structural calculations provided for review.Please B J \ TO RE: of Ix calculations. .ØIt is unclear how the lateral considerations for both wind and sgismic,will be Vu""o^plished.Ifyouintendtoprovideaprescripti@ancewithsection 602.10 of the 2015 International Residential Code, please indicate which method(s) and code on the .t f' I I t--Jtl--zzl^-,-^--It ts unuerstuuu tftul rrte yuu ,.-^-,lJ l:l-^ a^ -.-^ ¿l^^wuutu ltnE LU u;v tfte t1¿ .V \ section R602.10 the 20 1 5 IRC. Unþrtunately,is unclear which UJ nøtn@z.to.4,t tn plans. on the existing structure those on thespecifìc hold downs or anchors,includeal;oofrequffesbracing Ø 6)1.fr" proposed addition exceeds 500 square feet and will require "whole house" V-*"hunical ventilation in accordance with M1507.3. If this is intended to be an "ADu' the system is only required to ventilate the new portion, if this is truly an addition the system must accómmbdate the entire home. Please indicate on the plans. b, tt Ðt which codes sections and type of bracing to be used as identified in which code section the elected bracing is to require to complywith. entire section as there ore yery specific minimum dímensions and maximum spacing that brøcedwalls must comPlY with.take into 3. RECONCILED As the planning department has indicated in their review, this addition fits the description of anioAccesioryDwelling Unit". If this is the intent of the addition' you will n""d to provide a I hour fire separation between the units or interconnect the smoke and carbon monoxide detectors of the two units. AdditionallY, You will need to provide intendant water shut offand electrical panel that are readily accessible to the äccupants of the ADU without requiring special provisions to access through the primary dwelling. Please clariff and indicate on the plans' 4. RECONCILED Plan sheet 2 indicates an electric wall heater in the laundry room but does not appear to indicate how the rest of the addition will be heated. Please clariff and indicate oñ th. plans. ¡//þ r.L (þ25/4+¿tc \b Þ{ V It is understood that You would lilre to use a 6924 CFM Whole House exhaustfan' As reqùiredby sectíon M1507.3, the exhaustfan would only need to be ø continuously operating 90CFM exhaustfan, such as the one you ore ínstalling in the ProPosed latmdry room.If you intend to install an intermittentþ operatingfan, the CFMwill need to be increased in accordance with table M1507.3.3 (2). Please the whichyou choo;et-losttilize.-phçQ 3 trwçe I+//R¿at-ìne Ð 6 Please let me know if I can be of any further assistance' Sincerely, Eric Carter RECONCILED Carbon Monoxide detectors are required on each level of oútside every sleeping area. Please indicate on the plans' Additional comments may be generated upon the second review. home and PageZ of3