Loading...
2018-1312 Bohn Enclose Existing Garage.pdf DATE: October 12, 2018 TO: Josh Bohn, TLJ Construction FROM: Eric Evensen, Plans Examiner RE: Plan Check: BLD2018-1312 Project Address: 8711 184th Str SW Scope: Enclosure Existing Carport Structure - VB construction Please be advised that the building plans for the above referenced project have been approved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. This building plan review cannot be completed until we receive the following items: Proposed Floor Plan: 1. Concrete stem walls required in this review shall extend a minimum of 6” above the above the adjacent grade per R404.1.6. 2. Portal Frame with Hold-Downs – On the plans, in order to successfully resist North/South wind loads from the new garage walls, indicate and provide a 16” long portal frame with hold-downs per Figure R602.10.6.2 of the 2015 International Residential Code (IRC) on either side of the garage door opening to. Note this will leave a 16’-0” wide opening for the garage door. 3. Braced Walls – On the plan, in order to successfully resist East/West wind loads from the new garage walls, indicate that the base of the new North/South garage walls are secured through a pressure treated wood sill plate with ½ inch diameter anchor bolts at a minimum of 6 feet on center and located within 12 inches of the ends of each plate to new concrete curbs; anchor bolts shall be embedded 7”minimum into concrete per IRC R403.1.6. City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Page 2 of 2 Please be aware that once the above corrections are made, subsequent city review may identify further corrections. Please let me know if I can be of any additional assistance. Eric Evensen