2018-1371 Greene Deck.pdf
DATE: October 19, 2018
TO: Willie Franklin
frankstyme@gmail.com
FROM: Eric Carter, Plans Examiner
RE: Plan Check: BLD2018-1371
Project Address: 6921 163rd PL SW
Scope: Remove and Replace Entry Deck and Stairs.
Please be advised that the building plans for the above referenced project have been disapproved
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
information, clarifications, or changes are needed. Reviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter. Items that recur on this list appear in italics.
A complete review cannot be performed until the revised plans/documents, including a
written response in itemized letter format indicating where the ‘clouded’ or otherwise
highlighted changes can be found on the revised plans, have been submitted to a Permit
Coordinator.
Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
General:
The submitted plans do not appear to have included any structural documentation. Please
submit two copies of gravity calculations for the framing members.
A4.000:
1. The plans indicate a section view of 3/A5.00, this section does not appear to have been
included on the plans. Please clarify and change on the plans.
2. The deck footing plan indicates a “TapCon Bolt Embedment”. Please indicate on the
plans the size and embedment of the anchors on the plans.
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
Page 2 of 3
3. The deck framing plan indicates that a spiral stair case is intended to be installed as part
of the project, the code sections cited on the plans do not appear to be current. If you still
would like to incorporate the code section, please indicate the proper section from the
2015 International Residential Code.
A5.00
4. As indicated on 2/A5.00 the deck ledger is intended to be reutilized. The details indicate
bolts, but do not specify size or spacing. Please indicate the size and spacing on the
plans.
Additional comments may be generated upon review of the additional information submitted.
Please let me know if I can be of any further assistance.
Sincerely,
Eric Carter
Page 3 of 3