Loading...
2018-1658 Waterfront Center Building Non Struc 1 Beck.pdfBeck & Associates, PLLC Structural Engineering & Code Consulting 16425 SE 66th Street, Bellevue, WA 98006 ● beckpllc@msn.com ● PH: 206-313-3739 January 22, 2019 Leif Bjorback Building Official City of Edmonds 121 5th Avenue North Edmonds, WA 98020-3145 Subject: Edmonds Waterfront Center (Non-structural Review) Permit: BLD18-1658 Per your request, Beck & Associates has completed a non-structural review of the drawings and calculations for conformance with the 2015 International Building Code (IBC), as adopted and amended by the State of Washington (WSA) and the City of Edmonds (ECC). Our review of the plans and calculations indicates that corrections are necessary prior to permit issuance. The applicant should address the following comments in itemized letter format in addition to making corrections & revisions to the drawings. Corrections and revisions to the drawing should be clouded so that they are clearly identifiable. General 1) The plans need to provide design and detailing for the construction of all dropped ceilings, soffits, and suspended ceiling elements. If any of this will be provided as a deferred submittal to the City for review, the plans will need to be updated to indicate that this is the case. Deferred submittals are required to be reviewed/approved by the architect and engineer of record prior to submittal to the City for review. Construction of typical suspended ceilings should be comply with Technical Document 401 produced by the NW Wall & Ceiling Bureau. We recommend that a copy of this document be provided with the construction documents. 107.3.4.1 2) Every room or space that is an assembly occupancy is required to have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. On the Floor Plans, identify the location and proposed occupant load of each assembly occupancy. 1004.3 Drawing Sheets T1.3 – Building Code Information 3) Reference Chapter 6 – Types of Construction notes. South Wall ‘B’ is noted as having a proposed fire separation distance of 10’-0”. However, the Site Plan on sheet A1.1 identifies a fire separation distance (it appears to be incorrect) of 22’-1”. Provide coordination between sheets T1.3 and A1.1. Identify the correct fire separation distance as measured from the face of the building to the nearest property line. Table 602; 704 4) Reference the Parapet section. It is unclear on the plans how exception 4 of 705.11 will be met so that parapets are not required. Specify all elements on the plans and provide detailing to demonstrate that the requirements of the exception will be met. 705.11 BLD18-1658 (NS) January 22, 2019 Page 2 of 6 16425 SE 66th Street, Bellevue, WA 98006 ● beckpllc@msn.com ● PH: 206-313-3739 5) Reference the Accessible Means of Egress section. A note indicates that the elevator is not a part of the accessible route. While the elevator is not part of the accessible means of egress, it is a part of (and required for) the accessible route. The note should be updated accordingly. T1.4 – Building Code Information 6) Reference 2/T1.4 – Second Floor Occupant Loads and Exit Separation Diagram. Reference the Group A-3 occupancy and occupant load noted for the Game Room. The occupant load of the Game Room is required to be based on an occupant load factor of 15 sf/occupant as required by Table 1004.1.2. Please note that the occupant load factors of Table 1004.1.2 are maximums, resulting in minimum occupant loads for egress design. Based on the square footage, the occupant load of the Game Room will accordingly be 48. Revise the design and drawings accordingly. The Game Room will need to be provided with (2) exits, separated by 1/3-diagonal of the space since the resulting occupant load exiting the Game Room will exceed 49. 1004.1 7) Reference 4/T1.4. Egress from the Thrift Store is shown via a horizontal sliding door. Egress doors are required to be side-hinged swinging. In this case, it appears that a power-operated door in accordance with Section 1010.1.4.2, would meet code requirements. Revise the plans to demonstrate how egress from the Thrift Store will comply with the code. 1010.1.2, 1010.1.4.2 8) Reference 5/A1.4 – Second Floor Egress Diagram. When the folding partition between Multipurpose 1 and Multipurpose 2 is open, Door 217 is required to be the exit access door in order to maintain the required exit separation of the space. While 2/T1.4 shows Door 217 as being the exit access door, 5/T1.4 does not and incorrectly shows the occupants exiting through Door 216. Update the plan to show occupants exiting through Door 217 (into the Game Room) and then through Door 207 (the door from the Game Room). A1.1 – Site Plan 9) Identify the least fire separation distance on the west side of the building. A2.1 – First Floor Plan 10) Several section references are incorrect. Provide coordination. 11) Reference the DMarc room underneath the north stairs and the Storage Room underneath the south stairs (at the Coffee Kiosk). The walls and soffits within enclosed usable spaces under stairways (whether enclosed or unenclosed) are required to be protected by 1-hour fire-resistance-rated construction. 1011.7.3 a) Assemblies and detailing for the construction of the rated walls and soffits have been provided and code requirements are met. Revisions are not required. b) While the code does not specifically state that the doors are required to be 1-hour rated, it is our understanding that the doors to rooms under stairways are required to be 60- minute rated. Update the Door Schedule accordingly. 12) The exterior area along the south side of the building serves as an exit discharge and is defined as an egress court. This exterior wall is already required to be 1-hour rated due to the fire separation distance (less than 10’-0”). Additionally, all openings in the exterior wall are required to be protected by opening protectives having a fire protection rating of not less than ¾ hour where located within 10’-0” vertically of the level of the egress court. Update the BLD18-1658 (NS) January 22, 2019 Page 3 of 6 16425 SE 66th Street, Bellevue, WA 98006 ● beckpllc@msn.com ● PH: 206-313-3739 plans to identify all openings that are required to be provided with a ¾-hour rating. (louvers, Laundry Room window, Door 124, glazing adjacent to door 124, and Door 137). 13) The electrical room that serves the parking area is required to be designed to accommodate the electrical equipment and distribution required to serve a minimum of 20 percent of the total parking spaces with 208/240 V 40-amp electrical vehicle charging infrastructure. Please note that this requirement is to insure that the electrical room will be able to accommodate future electrical equipment and distribution. The equipment and distribution are not currently required to be installed. 427 A2.2 – Second Floor Plan 14) Several section references are incorrect. Provide coordination. 15) Reference the South Balcony a) An accessible route is required to be provided to the South Balcony. Provide dimensions and detailing that demonstrates that the threshold will meet accessibility requirements. 1104.3 b) Egress is required to be provided from the South Balcony at all times. If it is the intent to provide locking devices on the doors leading from the balcony (Doors 219 & 232), the plans will need to demonstrate how code requirements for egress will be met. 1004.5; 1010.1.9.5; 1010.1.9.7 16) Provide detailing for the condition where the floor intersects the 1-hour rated exterior wall. Provide detailing that demonstrates that the required 1-hour rating (rated from both sides) will be maintained. 602, 705 A2.3 – Roof Plan 17) Indicate on the Roof Plan how roof drainage will be addressed. Provide detailing for drains, scuppers, etc. Please be aware that secondary (overflow) drainage is required. Provide design and detailing for primary and secondary drainage. UPC 1101.12 18) The Roof Plan should be updated to identify the proposed distance of projections from the building face along the south elevation. This should be consistent with what is identified in the Building Code Info on sheet T1.3. A4.8 – Elevator Enlarged Plans & Sections 19) Reference 3/A4.8. The Elevator Control Room is required to be enclosed with 1-hour fire barriers constructed in accordance with Section 707 and horizontal assemblies constructed in accordance with Section 711. 3005.4 a) Identify the assemblies that will be utilized to provide the required 1-hour ratings and provide complete detailing for construction & inspection. b) Openings protection is required to be provided as for fire barriers. In this case, the door to the Elevator Control Room will need to be 45-minute rated. Table 716.5 c) Please be aware that construction supporting fire barriers and horizontal assemblies is required to be 1-hour rated as well. The path of the rated assemblies will need to be traced to and include columns/bearing walls, etc. 707.5.1, 711.2.3 BLD18-1658 (NS) January 22, 2019 Page 4 of 6 16425 SE 66th Street, Bellevue, WA 98006 ● beckpllc@msn.com ● PH: 206-313-3739 20) Provide complete detailing for the construction of the 1-hour elevator shaft walls at floor and roof intersections. Detailing will need to demonstrate that the required 1-hour rating is maintained. 3002.1 A5.1 – Exterior Wall Types 21) GA Assembly WP 3661 requires the insulation within the rated wall to be mineral fiber insulation. Detailing for walls that utilize this listed assembly (A2, A3, A4, A5, and A8) should be updated to specify that the insulation is required to be mineral fiber insulation. GA Explanatory Note #12 A5.3 – Slab; Floor/Ceiling & Ceiling/Roof Assemblies 22) Stair and Landing/Ceiling Assembly FC7b is required to provide a 1-hour rating. GA Assembly FC 5407 is specified. However, detailing required by FC 5407 (with TJIs) is inconsistent with the actual stair construction proposed. Provide a listed, tested 1-hour rated soffit (floor- ceiling) assembly that is consistent with the proposed construction. A6.1 – Accessibility Details & Notes 23) Reference 3/A6.1. Ambulatory accessible toilet compartments are required to be provided with vertical grab bars on each side of the compartment. Locate the vertical grab bars in the elevations and specify required dimensions. ICC A117.1-09, 604.10 24) Reference 7/A6.1. a) The seat in the shower must meet the dimensional requirements of ICC A117.1-09, 610. Specify all dimensions to demonstrate compliance. ICC A117.1-09, 608.2.3.2 b) The end wall grab bar is required to extend 30-inches from the back wall. This needs to be specified. ICC A117.1-09, 608.3.2 A6.2 – Enlarged Plans – Interior Elevations 25) Reference 1/A6.2. The plumbing chase between the bathrooms extends through the floor and creates a shaft. Identify the shaft assemblies to be utilized to provide 1-hour shaft construction. Provide complete detailing. A6.3 – Enlarged Plans – Interior Elevations 26) Reference 11/A6.3. A minimum clear height of 7’-6” is required to be provided at the Coffee Kiosk. This needs to be specified. 1208.2 A6.6 – Enlarged Plans – Interior Elevations 27) Reference 3/A6.6. The stage curtain is required to meet the flame propagation performance criteria of NFPA 701 or exhibit a maximum heat release rate of 100 kW when tested in accordance with NFPA 289, using the 20 kW ignition source. 806.4 a) This needs to be specified on the drawings. b) A copy of the report of the test results will be required to be provided to the building inspector/building official during construction. BLD18-1658 (NS) January 22, 2019 Page 5 of 6 16425 SE 66th Street, Bellevue, WA 98006 ● beckpllc@msn.com ● PH: 206-313-3739 28) Reference 1/A6.6. a) Specify riser heights and tread depths for the stairs leading to the Stage. 1011.5 b) Handrails are required to be provided on both sides of both stairs that lead to the Stage. Specify dimensions and all requirements. Provide detailing. 1011.11 A6.7 – Enlarged Plans – Interior Elevations 29) Reference 7/A6.7. At least 5% of the sinks in the Clinics are required to be accessible, requiring a front approach. Identify the accessible sink for the clinics and provide dimensions and detailing to demonstrate that a front approach, compliant with ICC A117.1-09, will be provided. 1109.3; ICC A117.1-09, 606 A8.1 – Door Types & Schedules 30) Specify hardware types in the door schedule and provide a door hardware schedule within the plans. 1010 31) All doors serving A occupancies with an occupant load of 50 or more are not permitted to be provided with a latch or lock other than panic hardware. Once panic hardware is specified for an A occupancy with an occupant load of 50 or more, all doors along the egress path to the exit discharge (including exterior gates) are required to be provided with panic hardware. Identify all doors that are required to be provided with panic hardware. 1010.1.10 Energy Code (2015 WSEC) 32) All building entrances are required to be provided with vestibules, with all doors opening into and out of the vestibule equipped with self-closing devices. Update the Door Schedule to specify self- closing devices for all doors opening into vestibules. This will include doors 129A, 129B, 126, 127, 118A, 118B, 123B, 100, 101, 102A, 103, 107, and 108. WSEC C402.5.7 Foam Plastic Insulation 33) Foam plastic insulation is required to have a flame spread index of not more than 75 and a smoke-developed index of not more than 450 where tested in the maximum thickness intended for use in accordance with ASTM E84 or UL 723. The plans need to be updated to specify these requirements for foam plastic insulation. 2603.3 34) Roof assemblies with foam plastic insulation are permitted, provided the assembly with the foam plastic insulation is a Class A, B, or C roofing assembly where tested in accordance with ASTM E108 or UL 790. Provide documentation that the proposed roof assemblies meet these test criteria. 2603.6 Please contact me should you have any questions. Respectfully, BLD18-1658 (NS) January 22, 2019 Page 6 of 6 16425 SE 66th Street, Bellevue, WA 98006 ● beckpllc@msn.com ● PH: 206-313-3739 Douglas Beck, PE, SE Beck & Associates, PLLC