Loading...
2019-0279 DAWSON (1).pdf DATE: May 8, 2019 TO: Joshua Brincko FROM: Eric Carter, Plans Examiner RE: Plan Check: BLD2019-0279 Project Address: 1132 Viewlands Way Scope: ADDITION SFR, VB Construction, Plumbing and Mechanical included. Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. Items that recur on this list appear in italics. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. General: The provided Jacuzzi specifications don’t not appear to provide the following required information. 1. The portable spa shall comply with APSP-14 as required by section R403.11 of the 2015 Washington State Energy Code. Please provide documentation to support compliance with APSP-14. 2. The portable spa must comply with International Swimming Pool and Spa Code. Section 305 requires provisions of a “barrier”. This can be achieved by a lockable safety cover that complies with ASTM F 1346. Please provide spec sheets for the desired lockable safety cover or other means of compliance with section 305 of the ISPSC. Please let me know if I can be of any further assistance. Sincerely, Eric Carter City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Page 2 of 2