2019-0304 Mullet (Strobl).pdf
DATE: April 23rd 2019
TO: Jacob Strobl
jacob@strobldesign.com
FROM: Eric Carter, Plans Examiner
RE: Plan Check: BLD2019-0304
Project Address: 18909 Olympic View Drive
Scope: ADDITION, SFR, VB Construction Plumbing and Mechanical
included
Please be advised that the building plans for the above referenced project have
been disapproveddisapproveddisapproveddisapproved for the purposes of obtaining a building permit. During a review
of the plans by the Building Division for compliance with the applicable building
codes, it was found that the following information, clarifications, or changes are
needed.... Reviews by other divisions, such as Planning, Engineering, or Fire, may
result in additional comments that require attention beyond the scope of this letter.
Items that recur on this list appear in italicsItems that recur on this list appear in italicsItems that recur on this list appear in italicsItems that recur on this list appear in italics.
A complete review cannot be performed until A complete review cannot be performed until A complete review cannot be performed until A complete review cannot be performed until the revised plans/documents, the revised plans/documents, the revised plans/documents, the revised plans/documents,
including a written response including a written response including a written response including a written response in itin itin itin itemized letter format emized letter format emized letter format emized letter format indicating where the indicating where the indicating where the indicating where the
‘clouded’ ‘clouded’ ‘clouded’ ‘clouded’ or otherwise highlighted or otherwise highlighted or otherwise highlighted or otherwise highlighted changes can be found on the changes can be found on the changes can be found on the changes can be found on the revised revised revised revised plansplansplansplans, , , ,
have been submitted to a Permit Coordinator. have been submitted to a Permit Coordinator. have been submitted to a Permit Coordinator. have been submitted to a Permit Coordinator.
Resubmittals must be made at the Development Services Department on the 2nd
Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from
8:30am-12pm on Wednesdays.
A3:
1. The Energy Code notes indicate a local exhaust fan with window vents will be the
means of “whole house ventilation”. The plans do not appear to indicate the
location, CFM, or hours of operation. Please indicate the location of the local
exhaust fan, CFM and operation.
2. The provided window and door schedules indicate a minimum U value of .30. The
window and door notes indicate a minimum value of .28. Please clarify and
indicate on the plans.
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
Page 2 of 3
3. In accordance with IRC R302.3, the ADU must be separated from the existing
residence with a minimum of 1 hour fire rated construction. Or as indicated on
page 3 of Handout P1 provide by the City of Edmonds, in lieu of the 1 hour
construction interconnected smoke and CO detectors can be installed in such a
manner that the actuation of one alarm will activate the alarms in both primary and
accessory dwellings. Please indicate on the plans which method will unitized on
this project.
4. Section 606.3 of the 2015 UPC requires an independent water shut off for each
unit. Please indicate on the plan the location of the water supply shutoff on the
plan.
Please let me know if I can be of any further assistance.
Sincerely,
Eric Carter