Loading...
2019-0448 Abedalla .pdf DATE: September 17, 2019 TO: Niran Abedalla FROM: Donovan Akau, Plans Examiner RE: Plan Check: BLD2019-0448 Project Address: 7815 202nd Place SW Scope: Remodel/Addition, R-3, VB Construction. Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require atten tion beyond the scope of this letter. Items that recur on this list appear in italics. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. Sheet 01-02 thru 01-04: 1. Please provide what has been remodeled in the kitchen/bath. The plans do not show existing and proposed work. 2. Typical stud wall framing detail appears to not reflect the Engineers calculations. Clarify/correct on set of plans. 3. The penetration detail for the chimney needs more clarification and detail. See Chapter 10 of the 2015 IRC and make corrections as to the type of chimney/fireplace to be installed. Please provide the location/detail of the Chimney on the elevation sheet 01-04 to meet Chapter 10 of the 2015 IRC. 4. Detail for the foundation/ slab typ. It states that the R10 insulation 2’ W at perimeter is not required at garage. Refer to Section R503/ Table R402.1.1 in the 2015 WSEC. Make corrections to ensure that the 2015 WSEC is meet. This same detail that is provided is not clearly stated on the plans as to where this is be located for this project. Please correct and identify on the foundation plans. 5. Foundation wall (A). Please indicate where wall (A) is located on the foundation plan sheet 01-03. 6. Please clarify the abbreviation’s HD.WD found in bedroom(s), great room and hall way. 7. HDU2 hold downs are indicated as typical. The Engineer states that a different type of hold down is to be used for the existing. Please clarify as to what hold down are to be used for both the existing and new additions. Indicate this clearly on the plans. 8. The S.D and CO located near kitchen area. See Section R314.3 in the 2015 IRC as for the location. Please make corrections. City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Page 2 of 3 9. It appears that the whole house Mech. Ventilation is based on table M1507.3.3 (1) and M1507.3.3 (2) it is indicated to see 1-7. Please clarify/correct. 10. Please indicate the location of the specific sheer walls on the plans. Clarify/correct the Shear wall schedule, it appears that the information provided in the Engineers calculation packet does not transfer to the set of plans. Please ensure that the shear wall that is intended for this project ids located on the plans. SW-6 is not mentioned in the Engineers packet. 11. They typical roof sheathing on 01-03 does not correspond with Engineers packet. Clarify/correct the member sizes and installation detail. 12. Floor diaphragm does not reflect on the plan sheet 01-03. Correct/clarify on plans as indicated in structural packet from Engineer of record. 13. In the Engineers packet it is calculated to add a URFP or FRFP at 4’ OC with a ½ “ Titan HD. Please indicate the minimum depth of the 1/2:” Titan HD 14. Please indicate on the plans where the STHD 14 RJ is to be located. Notes: 15. I recommend that the owner, designer and Engineer of record review the entire project and make corrections to all and any information that will be used for the construction of this project and make the appropriate changes to the plans/calculations. 16. Please have the Engineer of record stamp and sign as indicated on the calc ulation packet “The calculation are only valid with an original wet sta mp and signed in ink”. Please have the stamp from the Engineer to be legible as well. Upon review of the resubmitted documents, additional comments may be generated . Sincerely, Donovan Akau Page 3 of 3