2019-0603 Kanon Deck.pdf
DATE: June 19, 2019
TO: Foster Kanon
FROM: Eric Carter, Plans Examiner
RE: Plan Check: BLD2018-0603
Project Address: 23302 Humber Lane
Scope: New deck and roof structure.
Please be advised that the building plans for the above referenced project have been disapproved
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
information, clarifications, or changes are needed. Reviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter. Items that recur on this list appear in italics.
A complete review cannot be performed until the revised plans/documents, including a
written response in itemized letter format indicating where the ‘clouded’ or otherwise
highlighted changes can be found on the revised plans, have been submitted to a Permit
Coordinator.
Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
General:
1. The submittal does not appear to include the required supplemental structural calculation
packets. Please provide two sets of calculations that have been prepared and stamped by
the designing Engineer.
S2.1:
2. The 2x10 joist noted on the plans, spanning 11’ are overstressed for the anticipated
loads. These joists will need to be of a larger size or change the on-center spacing, please
take into account of a minimum of 10PSF of “dead load”, 60PSF of “live load”, and the
applicable “wet service” and “incising” factors when sizing your framing members.
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
Page 2 of 3
3. Lateral load connections are required per IRC 507.2.4. Please indicate the locations of
these connections on the plans.
4. It does not appear that a ledger detail has been provided on the plans. Please provide a
detail that indicates the size of the ledger, anchor spacing and pattern of fasteners on the
plans.
Please let me know if I can be of any further assistance.
Sincerely,
Eric Carter