Loading...
2019-0898 Aldercrest RTU.pdf DATE: August 1, 2019 TO: Lifetime Heating and Air Darrick Philip FROM: Eric Carter, Plans Examiner RE: Plan Check: BLD2019-0898 Project Address: 21400 72nd AVE W Scope: 2 New Roof Top Units . Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. Items that recur on this list appear in italics. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. General: 1. Provide on the plans details, and references to them, specifying the minimum required attachment (equipment-to-curb/curb-to-roof) of each of the components to resist lateral loads per American Society of Civil Engineers (ASCE) 7-16, Chapter 13. Please let me know if I can be of any further assistance. Sincerely, Eric Carter City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Page 2 of 2