2019-0992 519 Main Street.pdf Page 1 of 2 DATE: September 5, 2019 TO: Graham Baba Architects Andy Brown FROM: Eric Carter, Building Inspector RE: Plan Check: BLD2019-0992 Project: Tenant Improvement for Restaurant Project Address: 519 Main Street, Edmonds WA During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a permit coordinator in the Development Services Department. General: 1. Provide as part of a complete permit application submittal a copy of the required review approval letter from the Environmental Health Division of the Snohomish Health District for the proposed project per the City of Edmonds ‘Tenant Improvement Permit Submittal Requirements’. 2. Please be aware that separate permits will be required for Plumbing, Mechanical, Fire Sprinkler, Fire Alarm, and Type I hood suppression. A0.02: 3. The Occupancy Load Calculations table references “2012 SBC”. The occupancy loads will be calculated with table 1004.1.2 of the 2015 IBC. Please change the reference and any applicable table values to reflect the IBC table. 4. The stairs leading to the proposed basement do not appear to have the required handrails indicated on the plans. Please provide handrail details in accordance with IBC 1014 on the plans. A1.01: 5. The side view of toilet accessibility diagram has several dimensions that do not comply with section 604.5.1 of ANSI 117.1-2009. Please review and change the dimensions on the plans. City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Page 2 of 2 6. The sink height indicated in the accessibility diagram does not comply with section 606.3 of ANSI 117.1-2009 A2.01: 7. The proposed plans indicate the installation of two walk in coolers. As part of the submittal, please provide the specifications for the proposed coolers. 8. The proposed plans indicate that part of the existing basement/storage is to be used for a kitchen/prep area. This area will now be classified as an occupied space and will be required to meet the minimum ceiling height of 7’6” for egress as noted in section 1003.2 of the 2015 IBC. Please indicate the ceiling heights on the plans. If the existing ceiling heights are less than required, a determination by the Building Official will be required. 9. The proposed plans indicate a door at the bottom the stairs into the kitchen prep area. A landing is required at the bottom of the stairs. The location of the door does not provide the required landing. As part of the revised plans, you can remove the door or extend the walls to provide a landing as deep in direction of travel as the stair width. Please clarify and indicate on the plans. Please be aware that once the above corrections are made, subsequent city review may identify further corrections. Please let me know if I can be of any additional assistance. Thank you, Eric Carter Building Inspector