Loading...
2019-1078 10608 231st st sw.pdfDATE: September 12, 2019 TO: Ken Mattson FROM: Kevin Bloomfield, Plans Examiner RE: Plan Check: BLD2019-1078 Project Address: 10608 231st ST SW Scope: Accessory Structure Thank you for submitting your plans to the City of Edmonds for review. We have completed an initial review of the project mentioned above. For this project to move forward a few items will need to be addressed. Once a revised set of plans, including a written response to the list of the items contained in this letter are resubmitted, we can complete the review. Some items may require a review by other divisions, such as Planning, Engineering, or Fire and will be noted as such. Resubmittals can be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. To complete the review the following items will need to be addressed: Sheet 2: 1. The plans show new headers to be installed, please provide details for these headers. Information should include size of the header, the material they are made of and how it’s attached to the structure. A typical header detail is sufficient. 2. Due to the size of the header located over the arcadia door, calculations from a design professional will be required. 3. The plans reflect 14’ rafters with a 30” extension. Please provide structural calculations for the rafters. Typical detail is sufficient, show all connections and ties used. Include connection of 30” eave extension on low side of shed also. Show positive connections for rafters to top plate of wall. Call out any clips, ties or brackets you will use. A typical detail will be sufficient. 4. Please show connections and any other details for the top wall on the shed high side. G City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Page 2 of 2 5. Plans show a 2x6 plate on the concrete slab, 6 feet on center. The plans also indicate 2x6 joist 16” on center. It isn’t clear how they will connect. More details for the floor assembly are needed. This should include direction and spacing for floor joists and how they connect. Show all nailing, brackets and hangers used. 6. Please note if this is intended to be a conditioned space in the future, there will need to be a vapor barrier below the insulation under the floor. 7. Although smoke alarms and co detectors are not required, it is recommended to add one to the hall area between the shop area and the storage area. Consider using combination alarms. 8. Include a detail for all posts. This should show all connections, material used and size. 9. A landing is required at all exterior door exits. This includes main entrance, garden storage, water tank room and sliding door. R311.3 Floors and Landings at Exterior Doors. Please note any deviation from these plans after approval may need approval from a design professional for the change. To eliminate delays, if you find the need to deviate from these plans, please contact the building department so we can go over the change. If you need any clarification or have any questions at all, please feel free to call anytime. Kevin Bloomfield