Loading...
2019-1543 Leftcraft Type I hood.pdf DATE: December 30, 2019 TO: Pacific Stainless Products monarchtcorp@gmail.com FROM: Eric Carter, Building Inspector RE: Plan Check: BLD2019-1543 Project Address: 519 Main Street Project: LeftCraft Scope: Install type I hood/makeup air for commercial kitchen, VB construction – Fire suppression system under separate permit Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Only those sheets specifically referenced as follows need to be resubmitted. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. General: 1. The plans do not appear to provide any information regarding compliance with section C403.2.7.1 of the Washington State Energy code. As part of a complete submittal, please include; a. Documentation the Type I hood is in compliance with UL710. b. Replacement air does not exceed 10 percent of the hood air flow rate. c. The specified hood does not exceed the maximum net exhaust flow rates of table C403.2.7.1. City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Page 2 of 2 d. Demonstrate minimum compliance for transfer air and demands of proposed HVAC systems of the space. Page 1; 2. As indicated on page 1 of the submitted plans a MAU will be installed as part of the Type I hood system. The plans do not appear to indicate compliance with IMC 508.1.1. Please indicate the maximum temperature differential on plans. Thank you, Eric Carter