Loading...
2019-1545 McIntosh Residence.pdf DATE: December 12, 2019 TO: Kenneth McIntosh FROM: Kevin Bloomfield, Plans Examiner RE: Plan Check: BLD20191545 Project Address: 821 Laurel Way Scope: Basement Remodel Thank you for submitting your plans to the City of Edmonds for review. We have completed an initial review of the project mentioned above. For this project to move forward a few items will need to be addressed. Once a revised set of plans, including a written response to the list of the items contained in this letter are resubmitted, we can complete the review. Some items may require a review by other divisions, such as Planning, Engineering, or Fire and will be noted as such. Resubmittals can be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. To complete the review the following items will need to be addressed: General: 1. Calculations appear to conflict with the drawings. The beam in the bedroom in the NW corner shows two holes 4.5” in diameter in the beam on the plans. The calculations reflect one hole that has a 6” diameter. When reviewing the specs from Weyerhaeuser (Header and Column Specs Guide TJ-9000 and TJ-7000) they are very specific concerning location and size of boring into their PSL’s. The manufacture specs state a hole no greater than 2” and must be located in the middle third of the beam. Please identify the location on the plans and verify the calculations and plans reflect the same thing. 2. Washington State Energy Code 2015, Section R503 Alterations, the exiting storage area is being converted into a heated space which will need to comply with the requirements set by the WSEC 2015, specifically section R503. This section addresses alterations to an existing home. City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Page 2 of 2 The home will need to qualify for .5 credits. Please use Table 406.2 in the WSEC to determine how you will satisfy the credits required. Include this in the general notes. 3. Also include an elevation showing all side of the home (front back and sides) it is important to know what is going on above the area supported by the beams. This will allow us to confirm the calculations for the beams used in this project. Page A1 4. Show all required smoke detectors and CO alarms on plans. Follow sections R314.3 for smoke alarm placement and R315.3 for CO alarm placement. Smoke and CO alarms must be interconnected with the rest of the home, all floors. The location outside the bedrooms needs both Fire and CO alarm, a combination unit is an acceptable option in this location. 5. Plans reflect a non-conditioned (not heated) space to be converted to a conditioned (heated) space. Please indicate the mechanical equipment that will be heating this space, include model, efficiency and fuel type used. 6. The plans also show new egress windows in the bedroom and office. These must conform to the guidelines set by WSEC 2015. Include specs of windows being installed. If you need any clarification or have any questions at all, please feel free to call anytime. Kevin Bloomfield