BLOW DOOR TESTING
Date:
Time Started:
Location:
Building Type
Iinit:
Test:
Tester:
Tester Location:
Outside Air Temp:
Inside Air Temp:
Wind:
June 25,2019
2:32PM
201 Main Street, Edmonds, WA
Multi-Family
203#, Second Floor corner unit with one adjacent units
C om partm e ntalized Testin g
Retrotec 1000 Series
Front Entry
72"F
68 0F
Negligible
Test Results:
CFM50 cFA (SF)SLA
SLA
Limit
Ceiling
Hr (Ft)cv (cF)ACs0
ACS0
Limit
843 1L51 o.ooo22L 0.0003 8 9208 4.346 <+5.0
Notes:
The test resulted in an acceptable SLA of 0.000221 (limit is 0.00030) and an acceptable air
change rate AC50 of 4.346 (limit is 5.0).
Flow was noted at the electrical outlets and light switches. Leakage was also noted at the wall
heater and through the light openings.
Because compartmentalized testing was accomplished, it is reasonable that a percentage of the
leaks are from the adjacent units.
-2¿--
Steve Depew, PE
Depew, Inc.
D Depew, lnc.1834 SW 152"d, BuÌien, WA 98165 Pht206.229.7475 ww,deþewÞinc.com
1 of3
I EPEW
GLOSSARY
AC50 Air Changes per Hour at 50 pascals pressure differential
CFA Conditioned Floor Area
CFM50 Cubic Feet per Minute at 50 pascals pressure differential
Compartm e ntalize d Te sti n g
Testing of a single unit with a single fan allowing for leakage through both
exterior walls and adjacent interior conditioned spaces. See Figure I below
CV
Figure I
Conditioned Volume
Specific Leakage Area
sLA: (CFM5O X .0s5) / (CFA X t44)
SLA
Test Checklist
Close allwindows, doors and fireplace and stove doors.
Close all dampers including exhaust, intake, make-up air, backdraft and flue
dampers. Since you will be depressurizing the house, dampers in bath fans, etc.
will be sucked closed during the test and will therefore not negatively affect the
results.
Notes: The range hood was not sealed beyond the barometric damper. Both
bathroom exhaust fans were sealed. The drier vent was attached to the drier
and not sealed.
Make sure plumbing traps are filled with water.
COI]RTYARI)
Dl ou'".,,n..1834 SW 152"d, Burien, WA 98166 Pht206.229.7475 www,deÞewpinc.com
2of3
I EPEW
X Leave doors between heated areas open.
X Open access hatches to conditioned attics and/or conditioned crawl spaces.
Notes: N/A
X Seal exterior openings for continuously operating ventilation systems and heat
recovery ventilators.
Notes: The through wall heat pump did not require sealing.
X Turn off heating and cooling systems but do not seal supply or return registers.
Notes: N/A
X Adjust all combustion appliances so that they do not turn on during the test.
X lnstall the blower door in an exterior door opening and connect hoses from the
manometer to the blower door fan and the exterior pressure tap. See
m an ufactu rer's i nstru ctions for correct set-u p.
X Depressurize the house to -50 Pascals.
X Record the flow rate.