RE: Plan Check: BLD2018-1041 — 508 Main St. — Exterior Deck Serving Adjacent Restaurant
Dear Chuck Miller,
In response to your itemized review commentary we are submitting our response for review with the
following responses (written in bold) to your comments (written in italics):
Al
1. Change on the plans the specified minimum length in inches of the landing at the top of the ramp
from '44'to '48'per International Building Code (18C) 1012.6.3, Exception 2.
a. Dimension revised to show minimum length per IBC as well as actual
dimension (to be field verified per compliance with 1113Q.
2. IndIcate on the plans the maximum vertical r1se of 30 Inches of the ramp run per 1BC 1012.4.
a. Note added to indicate maxiumum vertical rise.
3 IndIcate on the plans the required handralls complying with 1BC 1014 (IncludIng extensions) on
both sides of the ramp per 1BC 1012.8.
a. Plans revised to indicate handrails along with notes per IBC requirements.
4. IndIcate on the plans the required mInImum width of 36 Inches between the handralls per 18C
1012.5.1.
a. Note added to indicate maxiumum vertical rise.
5 IndIcate on the plans the required edge protection for the ramp per 1BC 1012.10
a. Edge protection provided. Note indicating compliance per XBC added.
6 IndIcate on the plans the guard complying with 18C 1015116078 on the 'open'side of the ramp If
required per IBC 1015.2.
a. Guard indicated on plans along with note. To be field verified per
requirements per IBC 1015.2.
7 IndIcate on the plans the function of the 'new privacy screen wall'as a guard complying w1th 1BC
101511607.8 if required per 1BC 1015.2.
a. Privacy screening wall noted as guard on plans along with requirements per
1113C.
RESUB
SEP 13 2018
5700 Corson Ave S. Seattle WA 98108
M9CULLOUGH 206 443.1181
A R C H I T E C T S mcc'ullougharchitects.com
A2
8. InIdIcate on the plans the orientation of the decking boards such that the long dimension of the
elongated openings are place perpendIcular to the predominant d1rectlon of the travel per ICC
A 1171-2009 Section 032.3 - see also plan review comment '10'
a. Framing revised and turned ninety (90) degrees to accommodate a direction
of travel that complies with barrier free access per A117.1-2009. See A2 per
framing plans revisions.
9 Change on the plans the code table reference regarding the required Are resistance rating based
on Are separation distance from '601 'to '602' with justification that the proposed structure and
Its elements are, by definition, not an exterlor wall.
a. Code reference revised and note added. See plans.
10 Redesign the deck1floor framing to provide Support for the deckIng boards requIred to be
orlentedtocomplywlthICCA1171-20095ectlon3O23 The design must Include details
regardIng the required minimum construction (size, depth of bottom of looting below adjacent
grade, concrete reinforcement, etc.) of the Isolated footings, and the spectrIcs of framing
connections, such as the number, dlameter, and length of lag bolts used to connect the rim to
the posts.
a. Deck framing revised. See plan sheet A2. Additional details per footings and
connections provided.