Loading...
3786_001.pdfSeptember 11, 2018 Attn: Chuck Miller City of Edmonds 121 51h Ave N Edmonds, WA 98020 RESuI3 SEP 14 2018 13UILDING DEPARTMEN-1 CITY OF EDMONDS architecture -i design I received the correction notice for project #BLD20181021 dated September 7, 2018. Below are the requested corrections and locations on the drawings that they can be found: 1. 01 Sheet General Notes a. The code reference has been changed to read IBC rather than IRC. b. The word residential has been removed from the reference for the energy code. 2. 03 Egress Plan — Lower floor a. The "Waiting Area" on the lower floor plan has been updated along with the occupant load. b. The occupant load for "Business Area7 has been recalculated based on gross floor area. c. The existing lower floor has been converted to unoccupied basement. The note has been clouded on the plan. d. The existing lower floor has been converted to unoccupied basement. Egress requirements will not be required for the existing unoccupied basement. 3. 03: Building occupant load has been updated and clouded on sheet 03. 4. 03 Egress Plan — Main floor a. The occupant load has been recalculated based on gross floor area for "Business Occupancy". b. The Waiting area note has been changed from Gross to Net. c. The Area of Refuge has been eliminated from the front porch. 5. Al. 1 Lower floor plan a. A note has been added and clouded on the lower floor plan calling out the 1 hr fire rated walls within 10' of the property line. b. Window 3 and 4 have been updated. Refer to clouded notes on Al. 1, A1.3, and A2.0. c. The handrail has been added and noted on ALI and A1.2. d. A drinking fountain has been added and noted on both floors. See A1.1 and A1.2 for clouded notes. e. A note has been added to the plans indicating that the salon will use a linen service rather than the existing laundry in the lower floor. 'Me Ton-dinson Linen Supply or similar service will be used. f. A note has been added on sheet A1.1 and A1.2 in the public restrooms calling out a tankless point of use electric water heater under the lavatory counters. 6. ALI: The crawlspace ventilation code has been changed to IBC 1203.4. 7. A1.2 Main floor plan a. A detail and note has been added and clouded calling out the 1 hour fire rating for exterior walls. b. A handrail was added and noted on the new addition stair. Handrails have been added and noted on the stair to the storage area. c. A drinking fountain has been added and noted on both floors. See A1.1 and A1.2 for clouded notes. d. A note has been added to the main floor plan calling out the reception desk to meet ICC Al 17.1 section 904.3. e. A note has been added on section A/A3.0 and clouded. 'Me porch floor framing to remain and the guard to be rebuilt as a fascia mounted system to allow for 5' clear space. Wall section 2/A4.0 has been updated and the note clouded. The east elevation has been updated and clouded, see A2.0. f. The sidewalk/ramp slope has been reduced to less than a 6" rise. The note is clouded on the plans. g. The current grade is just under the 30" threshold. A note has been added for the builder such that if the grade changes and becomes more than 30", then the 42" guard 23020 Edmonds WaU, *113. Edmonds, WA OW20 I P. 206.542.37341 e. hekl0h2darchheds-com I w h?-dcrd*ects— is required. A note is clouded on A2.0. A note has been added on A1.2 in reference to the note on A2.0. 8. Al.3 Roof plan and window/door schedules a. The roof overhangs have been called out to be fire rated and clouded on A1.3. 9. A2.0 and A2.1: The lower floor has been noted and clouded as existing unoccupied basement See Al. 1 for clouded note. 10. A2.0 Exterior elevations a. A calculation has been added to the north elevation for the window area. The change has been clouded on A2.0. The window schedule has been updated and clouded on Al.3. The floor plan has been updated and clouded on Al. I. 11. A3.0 Building Sections a. Additional dimensions have been added to the building section and clouded. The existing lower floor has been called out as "existing unoccupied basemene' and clouded on the sections. 12. AM Building Sections a. A note has been added to indicate the eave is to be a I br rated assembly. 13. A4.0 Wall Sections a. A note has been added to wall section I/A4.0 to indicate restriction of 4" sphere. b. The note on l/A4.0 has been updated and clouded. The reference for this floor assembly is the "Typical floor assembly @ the new addition" per 3/A4.1. 14. A4.1 Wall Sections a. A 1 hr fire rated eave assembly has been added to A4.1. Reference to the rated eaves is clouded on sheet A1.3. b. A 1 hr fire rated wall assembly has been added to A4.1 and noted on the main and lower floor plans A1.1 and A1.2. c. The concrete slab at the existing detached garage will be demolished and replaced. R- 10 insulation will be installed per updated wall section on A4.1. Al.0 demo plan has been updated and clouded. 15. ELO Lower floor and main floor electrical plan a. Occupancy sensor controls have been called out on the lower floor electrical plan and clouded. b. The time switch controls have been called out on the lower floor electrical plan and clouded. c. The Lighting worksheet has been updated and included with the submittal. 01 has been updated to note the options 1 and 2 of the energy code, as well as additional information has been added and clouded on A1.1 and A1.2. 16. SLO — Refer to structural engineer's memo. IT S2.0 — Refer to structural engineer's memo. 18. S2.1 — Refer to structural engineer's memo. Note: All revisions are clouded on the drawings. I can be reached at 206-542-3734 or at heidQh2darchitcas.co with any fiirther questions, Regards, Heidi Helgeson Principal H2D Architecture + Design 23020 Edamda WaU, *113, Edmonds, WA 98020 1 p. 206.542.3734 1 e. he,60h2clarchitecta.corn I w h2darchitects.com