October 1, 2018
City of Edmonds
Attention: Chuck Miller, Senior Plans Examiner
Project: 10032 Edmonds Way — Project #BLD2018 0892 Westgate Village
Subject: Correction Notice #1
Per your correction notice dated July 02, 2018 our response is as follows:
Item 1:
Please see each sheet in the drawing set (MO.0-M4.2) without 'NOT FOR
CONSTRUCTION' notation in the bottom -right comer.
Item 2:
Please see added licensed engineer stamp in the title block of each sheet of the drawing
set (MO. 0- S 1. 1).
Item 3:
Please see added general note clouded with revision delta 6 on sheet MI. I. Future T.I.
work is to be completed under separate permit by others.
Item 4:
Please see sheet index updated with 'M2. 1', 'M3. 1', 'M3.2', & 'M3.3' clouded with
revision delta 6 on sheet MO.O.
Item 5:
a. Please see added note #1 on OSA Ventilation Calculations Table clouded with
revision delta 6 on sheet MO.2. OSA REQ values are calculated using the known
design occupancy density given on code compliance sheet 5/GOO2 of the
architectural set under 2015 IMC 403.3. 1. 1. Exception I
b. Please see added note #1 on OSA Ventilation Calculations Table clouded with
revision delta 6 on sheet MO.2. OSA REQ values are calculated using the known
design occupancy density given on code compliance sheet 5/GO02 of the
architectural set under 2015 IMC 403.3. 1. 1. Exception I
Item 6:
Please see added note (*) on Rooftop Unit Schedule clouded with revision delta 6 on
sheet MO.2. The weight values on the Rooftop Unit Schedule on sheet MO.2 are a sum of
the net weight of each unit and the approximate weight of that unit's accessories. Also,
please refer to the revised structural report which accounts for the weight values indicated
on sheet MO. 2. This structural report can now be found on added sheets S 1.0 and S 1. 1
clouded with revision delta 6.
OF_zr_;Jfk3=SUB
V% L_
NE �qe_ OCT 0 1 20%
LOING DEPARTMENT
6U8,11T-Y OF EDMONDS
0 sySTEM
Page 2 of 2
Item 7:
Please see corrected note #1 on the Misc Fan Schedule clouded with revision delta 6 on
sheet MO.2.
Item 8:
Please see updated building permit plans submitted to the City of Edmonds Permit Center
on 9/20/18.
Item 9:
Please see added note clouded with revision delta 6 on sheet MI. 1. The wall assembly is
not fire -rated and is only used for screening the exposed duct work in the main lobby. A
two-hour smoke/fire damper (FSD-1) will be installed where the 8" supply -air duct
penetrates the slab.
Item 10:
Please see updated building permit plans submitted to the City of Edmonds Pen -nit Center
on 9/20/18.
Item 11:
Please see updated building permit plans submitted to the City of Edmonds Permit Center
on 9/20/18.
Item 12:
a. Please see updated 'Exhaust Ventilation Calculations' and 'Exhaust Fan
Schedule' clouded with revision delta 6 on sheet MO.2. Exhaust fans EF-9 and
EF- 10 have been added to the design to provide code required ventilation to
'Public Restroom 429' and 'Public Restroom 430' respectively.
b. Please see updated building permit plans submitted to the City of Edmonds
Permit Center on 9/20/18.
Item 13:
Please see fire/smoke damper call -outs clouded with revision delta 6 on sheet M2.1
updated to read "FSD-3" in order to match the notation specified on sheet MO.3.
Please call if you have any questions or comments.