Subject: Building Plan Review Corrections PC6-571
Steve,
went a head and wrote up the thing I talked to you about earlier but after reading the letter provided from Dennis Bruce
the temporary shoring walls he talked about will also require calculations and plans. See my attached correction. Hopefully
who ever you have working on the retaining walls can also provide the information on the temporary shoring.
20060421050713.p
df (39 KB)
Jenny Readwin
Plans Examiner
City of Edmonds
425-77.1-0220
1
a� Endo City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: April 21, 2006
TO: Steve Lovell
Snlovell@comcast.net
FROM: Jenny Readwin, Plans Exami r
RE: Plan Check # 05-571
Project: Addition
Project Address: 8312 Talbot Rd.
During re -review of the above noted application, it was found that the following information,
corrections, or clarifications are needed.
Initial corrections 12/28/06
Second set of corrections 2116106
Third set of correction 3130106
Fourth set of corrections 4120106
1) ok
2) ok
3) ok
4) ok
5) Still need no response given. See attached structural comments from city consultant.
Respond to each item in writing.
• Structural Consultants Item #E What is the connection required for beam marked D to
the triple rafter? Nothing is specified at this time. Please add this information to the
drawings. Specify which THG hangeryouintend to use. There are several different
ones in the Simpson catalog. T
6) Still need no response -given. It is my understanding that you are working on this
item. Rockeries and retaining walls located in a critical area, regardless ofheight,_reguire a
separate permit. See enclosed handout for submittal requirements. Details and Engineered
.stamped calculations are required for review and it is possible that peer review will be
required.
7) Letter_ from Dennis Bruce, PE dated April 6, 2006 received April 13, 2006 says
that temporary shoring will be required. A temporary shorin_g plan and details
with Engineered stamped calculations are required (same as rockeries and
retaining walls).
Please redline plans or submit two (2) sets of revised plans/documents (affected sheets_only_) with
a written response to each of the above items to a Permit Coordinator.