Loading...
400 Dayton Bennett Properties.pdfI /) C. I S k) ", 121 5" Ave N Edmonds WA. 98020 12425 Meridian Ave, Evereft, WA 98208 Serving the cities of Brier, Edmonds, and Mountlake Terrace Department of Fire Prevention Comments To: 400 Dayton — Bennett Properties From: Karl Fitterer Assistant Fire Marshal Date: February 26, 2019 Re: Tenant Improvement South County Fire has completed the review of the plans for a second story tenant improvement at 400 Dayton St Edmonds, WA. BLD20190134 The review and comments are based on the following submittal documents: 1. 2015 International Existing Building Code 2. Edmonds City Municipal Code 3. 2015 International Fire Code This approval is in accordance to (IBC) International Building Code, Edmonds City Municipal Code (ECMC) and the (IFC) International Fire Code 1. A monitored Fire Alarm will be required IEBC 504 Level 2 alteration, ECIVIC 19.25.035 C Fire Alarms and Detection Svstems. In addition to the reauirements of Section 9072. an ainoroved monitored automatic fire alarm system shall be installed and maintained throughout all buildings, structures, floors, and suites described in this section. If conflicts exist between the IFC and this section, this section shall prevail. Fire alarm systems shall be installed per NFPA 72 and SCFs fire alarm standard. Partial area fire alarm systems are prohibited except where approved by the fire cod officia/. 2- In existina buildinas and structures that underao an addition where the new total fire area is 3000 square feet or greate 3- When required bV the International Existing Building Code (IEBC) for existing buildings an structures undergoing additions, alterations, repairs or changes of occupancy- The classification of work level shall be determined bv the buildina and fire code official Installed per IFC Section 907. And NFPA 72 I /) C. I S k) ", 121 5" Ave N Edmonds WA. 98020 12425 Meridian Ave, Evereft, WA 98208 Serving the cities of Brier, Edmonds, and Mountlake Terrace Department of Fire Prevention 2. Deferred Fire Alarm as stated on plans. 3. Fire Alarm Panel will be located in electrical room or mutually agreed area.. Fire Alarm Annunciator Panel will be located inside main entrance. A Knox type key box will be required at this main entrance. 4. Fire extinguishers are required at all exits and every 75 feet interior. 5. Building to finalize occupant load. Karl Fitterer CH Deputy Fire Marshal City of Edmonds Department of Fire Prevention kfitterer(a)southsnofire.orci 425-775-7720 425-551-1980