Department of Fire Prevention
Comments
To: 400 Dayton — Bennett Properties
From: Karl Fitterer Assistant Fire Marshal
Date: February 26, 2019
Re: Tenant Improvement
South County Fire has completed the review of the plans for a second story tenant improvement
at 400 Dayton St Edmonds, WA. BLD20190134 The review and comments are based on the
following submittal documents:
1. 2015 International Existing Building Code
2. Edmonds City Municipal Code
3. 2015 International Fire Code
This approval is in accordance to (IBC) International Building Code, Edmonds City Municipal Code
(ECMC) and the (IFC) International Fire Code
1. A monitored Fire Alarm will be required IEBC 504 Level 2 alteration, ECIVIC 19.25.035
C Fire Alarms and Detection Svstems. In addition to the reauirements of Section 9072. an ainoroved
monitored automatic fire alarm system shall be installed and maintained throughout all buildings,
structures, floors, and suites described in this section. If conflicts exist between the IFC and this section,
this section shall prevail. Fire alarm systems shall be installed per NFPA 72 and SCFs fire alarm
standard. Partial area fire alarm systems are prohibited except where approved by the fire cod
officia/.
2- In existina buildinas and structures that underao an addition where the new total fire area is 3000
square feet or greate
3- When required bV the International Existing Building Code (IEBC) for existing buildings an
structures undergoing additions, alterations, repairs or changes of occupancy- The classification of work
level shall be determined bv the buildina and fire code official
Installed per IFC Section 907. And NFPA 72
I /) C. I S k) ",
121 5" Ave N Edmonds WA. 98020 12425 Meridian Ave, Evereft, WA 98208
Serving the cities of Brier, Edmonds, and Mountlake Terrace
Department of Fire Prevention
2. Deferred Fire Alarm as stated on plans.
3. Fire Alarm Panel will be located in electrical room or mutually agreed area.. Fire Alarm
Annunciator Panel will be located inside main entrance. A Knox type key box will be required
at this main entrance.
4. Fire extinguishers are required at all exits and every 75 feet interior.
5. Building to finalize occupant load.
Karl Fitterer CH
Deputy Fire Marshal
City of Edmonds
Department of
Fire Prevention