4577_001.pdfNovember 04 2018 Timothy L Sadler AIA 809 Laurel Way Edmonds WA 98020 Mr. Leif Bjorback, Plans Examiner City of Edmonds WA Building Division 121 St�'Ave North Edmonds WA 98020 RE: Gravity Lounge Project Hello Leif: I am working with Elyssa Boyd on responding to plan review comments issued by you on October 29, 2018. Please see responses below in respect to these comments. 1: "Clarify the indicated 'Project Valuation'. It appears to be less than that anticipated by the represented construction and the indicated scope of work. The building construction valuation for the purpose of calculating permit fees shall include the total value of work, including fair market labor and materials for all alterations. These should include, but not be limited to relocating the restroom door, adding a dining/drinking bar, changes to exterior windows and doors, lighting, etc." Applicant Response: See table below clarifying scopes of work to be performed, market value estimates of these scopes and total value of the work to be performed as documented. Scope of Work Required Estimated Value of Work Furniture + Fixtures (Bar Top Construction, Seating, Tables & Chairs) $3,000.00 Pony Wall Construction $1,000.00 Restroom Door Relocation $800.00 New Lighting $500.00 Overhead Rolling Door $1,500.00 Painting and Finishes $2,000.00 Total Estimated Construction/Fitout Cost $8,800.00 2. "Indicate on the plans the proposed occupancy group, as well as the previous occupancy group. It appears the new occupancy will meet the definition of "B" occupancy as per IBC 303.1.1." Applicant Response: See notations on Sheet A-0.1 calling out previous Occupancy Group "M"(Merchantile) occupancy & proposed Occupancy Group "B" (Business) Occupancy. 3. "Each space needs to be labeled on the plans as to its use (i.e. storage, dining/banquet, stage, etc.)" Applicant Response: See notations on Sheet A-0.1 calling out individual floor plan spaces. 4. "Provide occupant load calculations on the plans. IBC 1004." Applicant Response: See notations on Sheet A-0.1 defining occupant load for the project. 5. "On the plans, show the type and swing of all doors. Indicate whether they are existing or new." Applicant Response: See notations on Sheet A-0.1 indicating door existing + new door swings. 6. On the plans, show the type of hardware for all doors. It will need to be lever handled or otherwise accessible. IBC 1010.1.9.1 Applicant Response: See notations on Sheet A-0.1 indicating hardware types for all doors. 7. At least one accessible entrance is required to the space. indicate which door that is or whether both exterior doors are accessible. IEBC 410.8.1 Applicant Response: See notation on Sheet A-0.1 indicating accessible entry to the space. 8. Indicate on the plans the distance between the end of the new Bar and the nearby structural column. The minimum distance shall be 32 inches per ICC A117.1 section 403.5. Applicant Response: See dimension on the plans calling out 32" minimum between end of the bar top and opposite face of the structural column. 9. Please clarify the note on the plans "Overhead window to other side down to floor." is this a new window, or overhead door perhaps? Add descriptions and details as necessary. Also, indicate the U-value showing compliance with WS Energy Code. Applicant Response: Notation for overhead door are removed. OHD to be constructed at a later date under a separate permit. 10. Please clarify whether the Proposed Deck is actually a patio on the existing paved surface, or a wood framed deck. Applicant Response: Notation for patio deck are removed. OHD to be constructed at a later date under a separate permit. 11. The alterations require accessibility upgrades for the building per WAC 51.50 (IEBC 410.7). On the plans, either a) clearly show that the interior accessible route of travel complies with current code, or b) provide upgrades per the previously referenced section. If you choose to use exception #1 of that section, provide a letter stamped and signed by the architect (reference the code exception), stating the overall project cost, 20% of the project cost, and list the accessibility upgrades that will be done as part of this permit as well as showing that the total cost of the upgrades is at least 20%. Note that the valuation established compliant with review comment #1 above will be used as the project cost. Possible features that could be considered for upgrades might include accessible toilets and sinks, restroom grab bars, door sizes and approach space, etc. Show the selected features on the plans. Applicant Response: Please see Sheet A-01 showing access to existing accessible toilet facilities in the building common area. 12. Separate toilet facilities are required for each sex where the occupant load exceeds 30 persons. (IBC 2902.2) The separate accessible restrooms are considered part of the accessible route and must be located where they can be accessed from within the tenant space or from the exterior of the building unless there are accessible restrooms that exist elsewhere in the building within a travel distance of 500 feet of the most remote location in the tenant space. The public shall have access to the accessible restrooms at all times that the building is occupied. If this is the case, provide a letter signed by the building owner stating the existing restrooms are indeed available as described in this paragraph. Applicant Response: Separate accessible toilet facilities exist within 500ft of the most remote location of the tenant space. See accessible route description on Sheet A-0.1. See attached letter from the building owner stating that existing restrooms are available per the criteria outlined in the review letter. Energy Code 13. Where the use in a space changes from one category to another, the installed lighting wattage shall comply with WSEC C405.4. Provide a completed energy form for Interior Lighting - Space - By -Space Method — LTG-INT-SPACE, available at neec.net. On the plans, show all lighting fixtures and corresponding wattages to show compliance with the energy code. Applicant Response: See attached completed WSEC Energy Form for Interior Lighting. 14. Indicate on the plans the required lighting 'controls' (occupancy sensors) per WSEC C503.6 and C405.2.1. Applicant Response: See notations on Sheet A-0.1 identifying locations of occupancy sensors per WSEC C503.6 Leif, we appreciate your prompt review of our resubmittal package. Please don't hesitate to contact me with questions. Cheers, please revert with questions. Timothy L. Sadler AIA 809 Laurel Way Edmonds WA 98020 timothysadlerggiiiail.com (206) 992-6198 Cc: Gravity Bar. 8382 REGISTERED HITECT F OT Y L . S DL R S .N TATE F WASHING CN � I , %V% 0 tZ,