Loading...
7.18.17 Vault - Sheet S1.pdfDESIGN CRITERIA VERTICAL LOADS ON VAULT LID: UNIFORM LIVE LOAD : = 150PSF *HS20 TRUCK WHEEL LOADS 13'-6" 14' to 30' *� I (FRONT IREAR REAR! TRACTOR TRAILER i TRACTOR : FRONT AXLE = 8,000 lb. SINGLE REAR AXLE = 32,000 lb. TRAILER : SINGLE REAR AXLE _ 321000 lb. * = DESIGN LIVE LOAD AND TRUCK WHEEL LOAD TO BE APPLIED INDEPENDENTLY AND IN COMBINATION WITH THE SOIL COVER DEAD LOAD. IMPACT & FATIGUE: DUE TO THE INACCESABILITY, INFREQUENT ACCESS OF SERVICE VEHICLES OVER THE LID, AND THE SOIL COVER OVER THE LID, INCREASES IN VEHICLE LOADS TO ACCOUNT FOR IMPACT & FATIGUE ARE NOT REQUIRED. SOIL COVER FOR SUBSTRUCTURE DESIGN: THE SUBSTRUCTURE WAS DESIGNED FOR A MINIMUM SOIL COVER OF 6" & A MAXIMUM SOIL COVER OF 30" FOUNDATION DESIGN; FOUNDATION DESIGN IS BASED ON THE FOLLOWING ASSUMED VALUES: ALLOWABLE BEARING PRESSURE: 3,000 PSF LATERAL EARTH PRESSURES ON DETENTION VAULT: DRAINED LEVEL BACKFILL AT REST CONDITION: 55PCF EFW ACTIVE CONDITION: 35PCF EFW SEISMIC PRESSURE COMPONENT: E = 12H PSF UNIFORM SATURATED SOIL DENSITY: 125 PCF SPECIAL INSPECTION PLAN GENERAL: SPECIAL INSPECTION BY A QUALIFIED INSPECTOR IS REQUIRED IN ACCORDANCE WITH THE 2015 IBC. QUALIFICATION: THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL. REQUIRED VERIFICATION & INSPECTION: THE SPECIAL INSPECTOR SHALL PERFORM THE VERIFICATIONS & INSPECTIONS NOTED IN THE SCHEDULE BELOW INSPECTION & TESTING SCHEDULE TYPES OF WORK FREQ. SECT IBC SECTION CAST IN PLACE CONC REINFORCING STEEL, PLACEMENT. P 1705.3 IF PLACEMENT OF CONCRETE C 1705.3 VERIFYING USE OF REQUIRED DESIGN MIX P 1705.3 TESTING OF THE CONCRETE FOR SPECIFIED STRENGTH, AIR CONTENT AND SLUMP C 1705.3 SOILS VERIFICATION OF SOIL -BEARING CAPACITY: INSTALLATION OF DRAINAGE SYSTEM: PLACEMENT & COMPACTION OF WALL BACKFILL. C 1705.6 FREQUENCY LEGEND C = CONTINUOUS P = PERIODIC SEE REFERENCES AND STANDARDS LISTED WITHIN THE VERIFICATION & INSPECTION SCHEDULE FOR MEANING OF PERIODIC AND CONTINUOUS INSPECTIONS, CERTIFICATE OF COMPLIANCE: THE SPECIAL INSPECTION AGENCY SHALL PROVIDE A FINAL LETTER CERTIFICATE OF COMPLIANCE STATING THAT THE REVIEWED WORK WAS COMPLETED IN ACCORDANCE WITH THE PERMITTED DOCUMENTS, SUBMITTAL OF REPORTS: ALL SPECIAL INSPECTION REPORTS AND TESTING REPORTS SHALL BE SUBMITTED TO THE OWNER, SITE STRUCTURES AND THE BUILDING OFFICIAL BY THE AGENCY PERFORMING THE INSPECTION OR TESTING. REINFORCING BAR MATERIAL REQUIREMENT: REINFORCING BARS: USE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60,EXCEPT AS NOTED ON THE DRAWINGS. FABRICATION AND PLACING REQUIREMENTS: BENDING: BARS SHALL BE BENT COLD. BARS PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT UNLESS NOTED OR SHOWN OTHERWISE OR AUTHORIZED BY THE ENGINEER. PLACING: REINFORCEMENT SHALL BE SUPPORTED AND TIED TO PREVENT DISPLACEMENT BY CONSTRUCTION LOADS OR BY PLACING OF CONCRETE. MAXIMUM SPACING OF SUPPORTS SHALL BE 3'-611. CONCRETE COVER: MINIMUM CONCRETE COVER FOR REINF. SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE: CONCRETE CAST AGAINST EARTH 3" CONCRETE CAST AGAINST FORMS AND EXPOSED TO EARTH 2" WET SETTINGS: REINFORCEMENT ANCHOR BOLTS, OR ANY EMBEDDED ITEM WITHIN THE CONCRETE, MAY NOT BE SET INTO THE CONCRETE AFTER IT HAS BEEN POURED WITHIN THE FORMS. LAP SPLICES: LAP ALL BARS 24" MIN UNLESS SHOWN OTHERWISE ON THESE DRAWINGS. GENERAL CONSTRUCTION MOTES CODE: VAULT DESIGN AND CONSTRUCTION SHALL CONFORM TO THE PROVISIONS OF THE 2015 IBC AS ADOPTED BY THE CITY OF EDMONDS, WASHINGTON. GENERAL DETAILS: CONSTRUCTION DETAILS NOT FULLY SHOWN OR NOTED SHALL BE SIMILAR TO DETAILS SHOWN FOR SIMILAR CONDITIONS. DISCREPANCIES: THE CONTRACTOR SHALL NOTIFY ENGINEER UPON FINDING ANY DISCREPANCY OR OMISSION IN THE DRAWINGS OR SPECIFICATIONS, SHORING & EXCAVATION: THE. CONTRACTOR SHALL 5F_ SOLEY RESPONSIBLE FOR ALL EXCAVATION PROCEDURES, INCLUDING LAGGING, SHORING AND PROTECTION OF ADJACENT PROPERTY, STRUCTURES, STREETS AND UTILITIES. WALL BACKFILL: PRIOR TO BACKFILLING VAULT WALLS THE CONTRACTOR SHALL HAVE CAST THE LID CONCRETE. BACKFILL SOIL: WALL BACKFILL SHALL BE WELL GRADED FREE DRAINING SOIL FREE OF ORGANIC MATERIAL. BACKFILL SHALL BE PLACED IN LIFTS OF NO MORE THAN 8 INCHES AND COMPACTED TO WITHIN 90% OF THE SOILS MAXIMUM DRY DENSITY. ALL COMPACTION OCCURING WITHIN 5' OF THE WALL SHALL BE COMPLETED USING HAND OPERATED MACHINERY. CONCRETE CONCRETE REQUIREMENTS: LOCATION STRENGTH MAX W/C RATIO WALLS, CIP LID 400OPSI @ 28 DAYS 0.50 FTGS & GRADE SLAB 3000PSI @ 28 DAYS 0.53 AIR CONTENT: CONCRETE EXPOSED TO WEATHER SHALL CONTAIN 5% +/-1X ENTRAINED AIR. MIX DESIGN: SHALL BE BASED ON FIELD EXPERIENCE OR TRIAL MIXTURES IN CONFORMANCE WITH THE SPECIFICATIONS. EXPOSURE CATEGORIES: FREEZING THAWING FO SULFATE SO PERMEABILITY P1 CORROSION PROTECTION Cl MATERIAL REQUIREMENTS: CEMENT: ASTM C150. ADMIXTURES: ACI 301. AGGREGATES: ASTM C33. WATER: ASTM C94. PLACING REQUIREMENTS: PLACING: PLACE CONCRETE AS NEARLY AS PRACTICABLE TO ITS FINAL POSITION T 0 AVOID SEGREGATION. DEBRIS: REMOVE ALL DEBRIS FROM FORMS PRIOR TO PLACING CONCRETE, CONSOLIDATION: CONSOLIDATE CONCRETE BY SUITABLE MEANS. THOROUGHLY WORK CONCRETE AROUND EMBEDDED ITEMS AND INTO CORNERS OF FORMS. CURING REQU:REMENTS. CURIV* CONCRETE SHALL BE MAINTAINED IN A MOIST CONDITION FOR A SUITABLE PERIOD OF TIME AFTER PLACEMENT. WEATHER CONDITIONS: ADEQUATE PRECAUTIONS SHALL BE TAKEN DURING HOT AND COLD WEATHER IN ACCORDANCE WITH THE SPECIFICATIONS. TYP WALL REINF x a m (V ADD #5x DIAG EA FACE A SHOWN " p E. SEE ,WGS PIPE N AND ELEVATION ADD ONE #8 VERT FULL HEIGHT REINF BAR EACH Av0 (2ti-#6x3'-4"@ 6"olc EA SIDE OF BLOCKOUT FOR FACE ABOVE & BELOW EA PAIR OF VERT BARS OPNG CUT AT THE BLOCKOUT. 2 WALL REINF @ PIPE PENETRATION. SCALE N/A 8" L 29'-4" 28'-0" 1 s1 n --- r-'><7 ' - ---------------------------------------------------------------------- -- 1011 THICK CIP CONC SLAB. TOP OF SLAB 8 a EL= 431.84 ITOV=431.01 (� \ - 1 9 TYP THROUGH OUT VAULT. .i ' 4 ca L-_--- _------ --- - -- -- .----- ----- ---- --- - ----------- ---------------------- rel VAULT LID PLAN 2' 81 SCALE 1/4" = 1'-0" 0' 4' 29'-4" 8" 28'-0" 8" 2 F24x12 St ------------------------------- '�-------------- - IBOV=425.51 IBOV=425.51 I I 1 5" THICK CONCRETE I - - i SLAB ON GRADc I X o N L I IBOV=425.31 IBOV=425.31LL 1 I 51 I IBOV=425.51 3 IBOV=425.5i I Ll=---- ------------ ---------------- --------------`-I 1 F24xl2 S1 5 VAULT FOUNDATION PLAN 2' 8' SCALE 1/4" = l'-0" 0' 4' #5 x24"x24" CORNER BARS TO MATCH HORZ WALL REINF TYP TYP WALL CORNER REINF. s,i Ns #4@18"o/c EA WAY CONC DOBIE OR CHAIR TYP GRADE SLAB SECTION 59 % SCALE 1-1/2"=1'-0" 102 2'-Ori TYPICAL VVALL--SECT-1-ON s sCALE N/A- PLAN KEYNOTES 1, 5" THICK CONCRETE SLAB ON GRADE REINF WITH #4 @ 18" o/c EA WAY. PLACE ALL REINF AT MID -DEPTH OF THE SLAB. CAST GRADE SLAB IN A SINGLE POUR. SEE 4/S1. 2, C,I.P. CONCRETE WALLS AT THE PERIMETER OF THE VAULT. SEE 1/S1 FOR THICKNESS & REINFORCING UNO. 3. THICKENED SLAB FOOTINGS TO BE CAST WITH THE GRADE SLAB. SEE WALL SECTIONS ON THIS SHEET FOR SIZE & REINF. 4, 10" THICK CAST IN PLACE CONCRETE LID. SEE WALL SECTIONS FOR REINF. 5, PIPE INLET OR OUTLET TO VAULT. SEE CIVIL DWGS FOR PIPE DIAM, LOCATION & INVERT ELEV. SEE 2/91 FOR WALL REINF @ PENETRATION. ADDITIONAL REINF IS NOT REQUIRED FOR PIPE PENETRATIONS LESS THAN 8" O.D. IF PLACED BETWEEN TYPICAL WALL REINF. 6. 24" DIAMETER OPENING TO ACCEPT RISERS, LADDER, RING AND LOCKING MANHOLE COVER PER CIVIL DRAWINGS. 7. ADD #5x5'-O" DIAGONAL BARS TOP & BOT ON ALL 4 SIDES OF OPENING AS SHOWN. 8. ADD (21#66'-0" @ 6"o/c TOP AND BOT AS SHOWN. 9. ADD i2i#6 @ 6"o/c BOT FULL LENGTH EA SIDE OF OPENING. LEGEND IBOV INSIDE BOTTOM OF VAULT ITOV INSIDE TOP OF VAULT LID CIP CONCRETE WALL CONCRETE SPREAD FOOTING F2012 24" WIDE x 12" THICK FTG. SEE 1/61 E- DOWNWARD SLOPE DIMENSIONS & ELEVATIONS THE CONTRACTOR AND HIS SUBCONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL DIMENSIONS AND ELEVATIONS SHOWN ON THESE DRAWINGS WITH THE CURRENT PERMITTED SET OF CIVIL DRAWINGS, AND SHALL NOTIFY BOTH THE CIVIL & STRUCTURAL ENGINEERS IN WRITING OF ALL DISCREPANCIES BETWEEN THE CIVIL DWGS AND THESE DWGS PRIOR TO CONSTRUCTION. WALL SECTION GENERAL KEYNOTES 101, 10 THICK CAST IN PLACE CONCRETE SLAB 102, FINISHED GRADE. ELEVATION VARIES. SEE DESIGN CRITERIA ON SHEET 51 FOR APPROXIMATE SOIL DEPTHS OVER THE VAULT LID IN ADDITION TO THE CIVIL DWGS FOR FINAL GRADE ELEVATIONS, 103. 4" m PERFORATED PVC FOOTING DRAIN. PLACE FTG DRAIN AT I.E.=426.52. ROUTE DRAIN TO DISCHARGE SHOWN ON CIVIL DWGS. 104. APPLY PREFABRICATED DRAINAGE PANEL (DELTA -DRAIN OR EQUIVALENT) TO ALL PERIMETER VAULT WALLS. EXTEND DRAINAGE PANEL OVER THE FULL HEIGHT OF THE WALL. 105, PROVIDE CONTINUOUS 4" PVC WATERSTOP - RIBBED w/ CENTER BULB AT THE BASE OF ALL WALLS. INSTALL WATERSTOP IN ACCORDANCE WITH ALL MANUFACTURER'S INSTRUCTIONS. PLACE AT THE CENTER OF THE WALL. 106. SEE FND PLAN FOR GRADE SLAB REINF. RECEIVV_-D WALL SECTION jut.' a 201 REINFORCING KEYNOTES ENCdNEENt* DIVISI 201. 8" THICK CONCRETE WALL. REINF w/ #5@12"0/c HORZ & #5@16"o/c VERT. PLACE VERT REINF AT THE CENTER OF THE WALL. LAP ALL HORZ BARS 24" MIN @ SPLICE LOCATIONS. PROVIDE (2)-#5 CONT HORZ BARS @ THE TOP OF THE WALL. EXTEND VERT, REINF. 8.5" INTO THE LID POUR. PROVIDE STD HOOK AT END OF BAR EMBEDED INTO FTG. EMBED VERT REINF 9" INTO 12" THICK FTG 202, 24" WIDE x 12" THICK PERIMETER WALL FTG, CENTER ON WALL. REINF w/ (2)45 CONT. LONGITUDINAL BARS & #4@16"o/c TRANSVERSE. 203. (3)-#5 LONG TOP AS SHOWN. 204. #6@12"o/c BOT TRANSVERSE t RUNNING N-S 1. EXTEND 6" MIN ONTO 8" WALLS AT PERIMETER OF VAULT. 205. #5@12"o/c BOT LONGITUDINAL TO BE PLACED OVER TRANSVERSE REINFORCING I RUNNING E-W ). EXTEND 6" MIN ONTO 8" THICK WALLS AT THE PERIMETER OF THE VAULT, 206. #4x30"x38"@18"o/c WALL TO SLAB DOWELS. wu z a J Q W a 0 ix CL