Loading...
ACCO Eng. letter dated 5-22-07.pdfRECEIVED MAY 212007 PERMIT COUNTER 22 May, 2007 To: Freiheit & Ho Architects, Inc., P.S 10230 NE Points Drive, Suite 300 Kirkland, WA 98033 (425) 251-9680 (425) 251-0949 Fax Attn.: Rick Grimes From: Tim Garoutte, P.E. Subject: Stevens Health Care Center Request fo Alternate Design HVAC Equipment within a Corridor engineered systems 253 / 854-8444 Voice 253 / 854;,8220 Fax 835 N. Central Avenue Kent, Washington 98032-3099 We have received and reviewed the May 14th letter from the City of Edmonds regarding the proposed alternate design. Item 2: Letter of Concurrence As the Mechanical Engineer of Record for this project, ACCO Engineered Systems has reviewed the proposed Alternate Design and concurs that the proposed alternate design meets the intent of the applicable codes and is compatible with the mechanical system design and equipment. Item 3: Alterations to Existing Mechanical Drawings After reviewing the proposed alternate design with the fire alarm contractor, general contractor, and project architect it was determined that no modifications to the mechanical drawings were required based on the alternate design approach that was chosen. The alternate design relies on the fire alarm system, smoke detectors and interlocks with roll down doors to achieve the objective of preventing smoke from entering the corridor. The sequence of operation resides in the fire alarm control panel and devices necessary to accomplish isolation of the heat pumps are shown in the revised fire alarm drawings. Tim Garoutte, P.E. Engineering Manager ACCO Engineered Systems taaroutte0accoes.com (253) 854-8444 OurPlafinum Fs18blMed 1934 �ebSatimB //� annNef license OWCOC11310 20Years ry M the Pacific Nadhwesf