Ace Hardware OMT.DOC EDMONDS FIRE DEPARTMENT MEMORANDUM Date: March 18, 2009 To: File From: Mike Smith, Fire Marshal 425-775-7720 th Subject: Ace Hardware T/I 201 5 Ave S The Fire Department has the following comments: 1) Show locations of portable fire extinguishers minimum size 2A10:B:C 2) Show emergency lighting with two power sources 3) Identify on the plans the locations of Flammable and Combustible Liquids, Glue and Mastics, Aerosols, Pesticides and Fertilizers, any other Hazardous Materials as identified by the IFC, and overflow storage. (Storage Plan) 4) Please reference 2006 IFC Sections 2804, 2703, and 3404 for permissible amounts, storage arrays, and storage heights on shelving.