Anderson Office Bldg.DOC
EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: November 21, 2008
To: File
From: Mike Smith Acting Fire Marshal 425-775-7720
Subject: Andersen Office Building BLD20080635
The Fire Department has reviewed the plans under the 2006 IFC and the ECDC and
has the following comments:
1) Apply for a Fire Connection Permit. The water purveyor for this project is
Olympic View Water District. Verify with them the location of the backflow
assembly (in building or in a vault street side). Also verify with your fire sprinkler
contractor if a 2 inch fire line (as shown on the civils) will be sufficient in size to
supply the fire sprinkler system for the building.
2) Portable fire extinguishers (minimum size 2A10B:C) required in the building.
Two per floor and one in the garage should be sufficient.
3) Fire Sprinkler, Fire Alarm and Fire Protection Footprint can be deferred
submittals.
4) Show location of the building address (4 inch or larger numbers, 1 inch stroke
with contrasting background)
5) A Fire Department lock box will be required for emergency entry.