PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: October 25, 2007
TO: Robert Cull
E-mail: Robert@themolnickgroup.com
FROM: Ann Bullis, Assistant Building Official
RE: Revision to Permit 2007-1005
Project: Bella Coola Tenant Improvement
th
Project Address: 654 5 Ave S, 300
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit to Theresa Umbaugh, Permit Coordinator.
1.Note the building address on the plans.
2.Note the Type of Construction, occupancy and occupant load of the tenant space.
3.If the tenant is known at this time, please provide the business name for City files.
4.Note the uses of space on the floor plan.
5.Provide wall construction detail showing anchoring of the walls to the floor and floor-ceiling
structure above.
6.Door to southeast corner office must meet accessible maneuvering clearances per ICC/ANSI
A117.1 section 404.2.3 (dimension 12 clearance on the push-side of the door).