bld 20061106 and 1107 bldg 6-7 plumbing.doc
City of Edmonds
TH
121 5 AVENUE NORTH • EDMONDS, WA 98020 • (425) 771-0220 FAX(425) 771-0221
Website: www.ci.edmonds.wa.us
DEVELOPMENT SERVICES DEPARTMENT
Planning • Building • Engineering
Plan Review Comments
Plan Check : Date:
# BLD 20061106 & 1107 16 Oct 06
Project Name/Address:
Pt. Edwards: 31 and 41 Pine St
Contact Person/Address/Fax: fax/e-mail
: Ross Woods : ross@triaddev.com
Reviewer: Division:Engineering
Lyle Chrisman, Engineering Program Manager
The subject application has been reviewed but cannot be completed until the following items have been
addressed/corrected. Please resubmit 3 sets of revised drawings to a Development Services Permit
Coordinator.
1. Provide invert elevations at the end of the run and at each point where pipe size changes. Earlier discussions with
Longitude 122 on the sanitary sewer line for these buildings, indications were that the minimum 2% grade could not
be achieved and that an 8” would be used the entire run in order to get sufficient flow to the sewer manhole. Also,
the minimum sanitary sewer lateral size allowed is 6”. A portion of the lateral shows 4”.
__________________(Attach fax transmittal)
DATE FAXED
PAGE ____ OF ___