SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-28 REV. 3 10-1-02 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE - This chart is for general reference only. See complete details for each type of hazard. Hazard Duct or Transition (Single Nozzle) ► Duct or Transition (Single Nozzle) ► Duct or Transition (Dual Nozzle) Electrostatic Precipitator (At Base of Duct) ► Plenum (Horizontal Protection) ► Plenum (Horizontal Protection) J Plenum ► (Vertical Protection) Fryer/Split Vat Fryer" Maximum Hazard Dimensions Length — Unlimited Perimeter — 50 in. (127 cm) Diameter —16 in. (40.6 cm) Length — Unlimited Perimeter — 100 in. (254 cm) Diameter — 31 7/8 in. (81 cm) Length — Unlimited Perimeter —150 in. (381 cm) Diameter — 48 in. (122 cm) Individual Cell Length —1Oft. (3.1 m) Length — 6 ft. (1.8 m) Width — 4 ft. (1.2 m) Length — 4 ft. (1.2 m) Width — 4 ft. (1.2 m) Maximum Size (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity Medium Proximity Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity Low Proximity Maximum Size (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) ©l igh Proximity VTY OF EDMONDS BUILDING DEPARTMENT DDRESS-j �IPROVED �DATE:, Minimum Nozzle Nozzle ant Heiahts 1 — 1 — 2 — 1 — 1 — 1 27 — 47 in. 1 20 — 27 in. SC51V D im 16 2004 j)FRmff COUNTER 1 21 — 34 in. 1 13 —16 in. 1 25 — 35 in. (64-89 cm) Nozzle Tip Nozzle Stamping — Part No. Flow No. 430912 1100 419337 2W 419337 2W 419334 1 /2N 419335 1N 430192 1100 419336 1W 419336 1W 419339 230 419340 245 419338 3N 419342 290 419338 3N -� opy 4-14.Lj r - SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-29 1NEESE=10-1-02 REV 3 'ozzle Application Chart (Continued) Minimum Nozzle Tip Maximum Hazard Nozzle Nozzle Nozzle Stamping — Hazard Dimensions Quantity HeiahtsPart No. Flow No. Fryer/Split Vat Fryer** Maximum Size (with drip board) 21 in. (53 cm) x 14 in. (36 cm) (Fry Pot must not exceed 15in. x14in. (38 cm x 36 cm)) High Proximity 1 27 — 47 in. 419339 230 Medium Proximity 1 20 — 27 in. 419340 245 Maximum Size (with drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in. (49.5 cm) (Fry pot side must not exceed 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity 1 21 — 34 in. 419338 3N Low Proximity 1 13 — 16 in. 419342 290 Maximum Size (with drip board) 18 in. (45.7 cm) x 27 5/8 in. (70.2 cm) High Proximity 1 25 — 35 in. 419338 3N (64-89 cm) Range Longest Side 1 30 — 50 in. 419333 1 F 28 in. (71 cm) (76 — 127 cm) Area — 336 sq. in. 40 — 48 in. (2168 sq. cm) (102 — 122 cm) (With Backshelt) Longest Side (High Proximity) 1 40 — 50 in. 419340 245 28 in. (71 cm) (102 — 127 cm) Area — 672 sq. in. (4335 sq. cm) Longest Side (Medium Proximity) 1 30 — 40 in. 419341 260 > 32 in. (81 cm) (76 — 102 cm) Area — 768 sq. in. (4955 sq. cm) - Longest Side (Low Proximity) 2 15 — 20 in. 419342 290 36 in. (91 cm) (38 — 51 cm) Area — 1008 sq. in. (6503 sq. cm) For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11. SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-30 REV. 3 10-1-02 Nozzle Application Chart (Continued) ► Minimum Nozzle Tip Maximum Hazard Nozzle Nozzle Nozzle Stamping — Hazard Dimensions Quantit Hei hts Part No. Flow No. Griddle Longest Side (High Proximity) 1 30 — 50 in. 419341 260 48 in. (122 cm) (76 —127 cm) Area —1440 sq. in. (perimeter (9290 sq. cm) located) Longest Side (High Proximity) 1 30 — 50 in. 419342 290 30 in. (76 cm) (76 —127 cm) Area — 720 sq. in. (center located) ' (4645 sq. cm) Longest Side (High Proximity) 1 35-40 in. 419335/417332 1N/1NSS 36 in. (91 cm) (89 —102 cm) Area —1080 sq. in. (perimeter. located) ► (6968 sq. cm) Longest Side 1 20 — 30 in. 419342 290 (Medium Proximity) (51— 76 cm) 48 in. (122 cm) (perimeter Area —1440 sq. in. located) ► (9290 sq. cm) Longest Side (Low Proximity) 1 10 — 20 in. 419343 2120 48 in. (122 cm) ' (25 — 51 cm) Area —1440 sq. in. (perimeter (9290 sq. cm) located) Chain Broiler' Longest Side — 34 in. (86 cm) 2 10 — 26 in. 419336/417333 1 W/1 WSS (Overhead Protection) Area —1088 sq. in. (25 — 66 cm) (7019 sq. cm) Chain Broiler Length — 43 in. (109 cm) 2 1 — 3 in. 4193351417332 1 N/1 NSS (Horizontal Protection) Width — 31 in. (79 cm) (3 — 8 cm) Gas -Radiant Char -Broiler Longest Side — 36 in. (91 cm) 1 15 — 40 in. 419335/417332 1 N/1 NSS Area — 864 sq. in. (38 — 102 cm) (5574 sq. cm) Electric Char -Broiler Longest Side — 34 in. (86 cm) 1 20 — 50 in. 419335/417332 1 N/1 NSS Area — 680 sq. in. (51 —127 cm) (4388 sq. cm) Lava -Rock Broiler Longest Side — 24 in. (61 cm) 1 18 — 35 in. 419335/417332 1 N/1 NSS Area — 312 sq. in. (46 — 89 cm) (2013 sq. cm) Natural Charcoal Broiler Longest Side —. 24 in. (61 cm) 1 18 — 40 in. 419335/417332 1 N/1 NSS Area — 288 sq. in. (46 —102 cm) (1858 sq. cm) Lava -Rock or Natural Longest Side — 30 in. (76 cm) 1 14 — 40 in. 419338 3N Charcoal Char -Broiler Area — 720 sq. in. (36 —102 cm) (4645 sq. cm) Minimum chain broiler exhaust opening —12 in. x 12 in. (31 cm x 31 cm), and not less than 60% of internal broiler size. SECTION IV — SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-31 10-1-02 REVS Nozzle Application Chart (Continued) Minimum Maximum Hazard Nozzle Nozzle Hazard Dimensions Quantity Heights Wood Fueled Char -Broiler Longest Side — 30 in. (76 cm) 1 14 — 40 in. Area — 720 sq. in. (36 — 102 cm) (4645 sq. cm) Upright Broiler Length — 32.5 in. (82.5 cm) 2 — Width — 30 in. (76 cm) Salamander Length.— 32.5 in. (82.5 cm) 2 — Broiler Width — 30 in. (76 cm) Wok 14 in. — 30 in. (36 — 76 cm) 1 35 — 45 in. Diameter (89 — 114 cm) 3.75 — 8.0 in. (9.5 — 20 cm) Deep - 11 in. — 24 in. (28 — 61 cm) 30 — 40 in. Diameter (89 — 102 cm) 3.0-6.Oin. (8-15.2cm) Deep Nozzle Tip Nozzle Stamping — Part No. Flow No. 419338 3N 419334 1/2N 419334 1/2N 419341 260 419335/417332 1 N/1 NSS SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-1 10-1-02 REV.5 SYSTEM SELECTION GUIDE NOTE: System options do not cover all conceivable variations.They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3-tank systems, etc., other tanklcartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. Total Tank Type of Carbon Dioxide Nitrogen Flow No.' Quanti System Type of Hardware Cartridge Required Cartridge Required 1-5 1 Single 1.5 Gal. Reg. Release 101-10 (423439) LT20-R (423429) 6-11 1 Single 3.0 Gal. Reg. Release 101-20 (423441) LT30-R (423435) 12-16 2 Double 1.5 Gal. Reg. Release. 101-30 (423443) Double (423493) 3.0 Gal. AddftionalTank 17-22 2 Double 3.0 Gal. Reg. Release 101-30 (423443)" Double (423493) 3.0 Gal. Additional Tank 23-33 3 Multiple 3.0 Gal. Reg. Release 101-20 (423441) LT30-R (423435) 3.0 Gal. Reg. Actuator 101-30 (423443)"- LTA-101-30 (423491) 3.0 Gal. Additional Tank 23-27 3 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT20-R (423429) (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)"' LTA-101-30 (423491) 3.0 Gal. Additional Tank 28-33 3 Multiple 3.0 Gal. Reg. Release N/A Double (423493) (Optional) (2) 3.0 Gal. Additional Tanks 34-38 4 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423435) 3.0 Gal. Reg. Actuator N/A LTA-101-30 (423491) Double 3.0 Gal. Tank Box 34-38 4 Multiple 1.5 Gal. Reg. Release 101-30 (423443) Double (423493) (Optional) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)"' LT-A-101-30 (423491) 3.0 Gal. Additional Tank 39-44 4 Multiple 3.0 Gal. Reg: Release 101-20 (423441) LT30-R (423435) 3.0 gal. Reg. Actuator N/A LTA-101-30 (423491) Double 3.0 Gal. Tank Box 39-44 4 Multiple 3.0 Gal. Reg. Release 101-30 (423443)" Double (423493) (Optional) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)-'- LTA-101-30 (423491) 3.0 Gal. Additional Tank 45,49 5 Multiple 1.5 Gal. Reg. Release 101-30 (423443) Double (423493) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator N/A LT-A-101-30 (423491) Double 3.0 Gal. Tank Box 45-49 5 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT20-R (423429) (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)"* LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)"- LTA-101-30 (423491) 3.0 Gal. Additional Tank - Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system. _ ^ If tanks are manifolded, only a'double tank' nitrogen cartridge (Part No. 423493) can be used. •^ If tanks are manifolded, enter an LT-A-101-30 nitrogen cartridge (Part No.423491) or a double tank cartridge (Part No.423493) can be used. rh cx ^� r• Lu =VIA tit t,s