bld20060695 - Pt Edwards 21-31-41 Pine Grading-Walls_2_.pdf City of Edmonds TH 121 5 AVENUE NORTH • EDMONDS, WA 98020 • (425) 771-0220 FAX(425) 771-0221 Website: www.ci.edmonds.wa.us DEVELOPMENT SERVICES DEPARTMENT Planning • Building • Engineering Plan Review Corrections Application : Date: # bld20060695 January 23, 2008 Project Name/Address: Pt Edwards – 21, 31 and 41 Pine Street – Retaining Wall, Shoring & Grading Contact Person/Address, Fax or E-mail: Valerie Sargent / vsargent@weberthompson.com Reviewer: Jeanie McConnellDivision:Engineering During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit three (3) sets of revised plans/documents with a written response to each of the items below to Marie Harrison. ** Please provide a written response to the corrections as requested. 1.1/23/08 - City records state plan revisions were clouded 1/14/08. One plan sheet was clouded with yellow highlighter with no reference to a revision number. Please cloud/provide reference to a revision number so future copies of plans will clearly show what is being revised with this submittal. 10/10/07 comment - Please “cloud” plan revisions that are under review this submittal. · 2.1/23/08 – This issue is being handled by the City Building Division and Consultant. 10/10/07 comment - Per City Ordinance 3663, no rockery shall be placed against fill and no rockery · shall support a surcharge. The revised plans show the rockery being placed within a structural fill area as well as supporting a surcharge from the pool and lawn/geo block fire lane. Retaining walls will be required in the proposed rockery locations. Please refer to handout B62 for Retaining Wall Design requirements. The rockery will need to be designed and stamped by a licensed engineer. Design and supporting calcs will need to be submitted to the City for review. 3.1/23/08 – This comment was not addressed. 10/10/07 comment - A 2” domestic water meter is shown to be located within the lawn/geoblock fire · lane. Please relocate the water meter outside this driveable surface. 4.1/23/08 – This comment was not addressed. 10/10/07 comment - The geoblock sub-base shall be per manufacturers specs and/or requirements · established by the engineer of record. Please confirm that 6” crushed rock sub-base is acceptable. Please contact me at 425-771-0220 or by e-mail at mcconnell@ci.edmonds.wa.us if you have specific questions regarding these plan corrections. DATE E-MAILED 1/23/08 PAGE 1 of 1