BLD20060827 Fire Consult Rvw.pdfEagl'e Eye Consulting Engineers, P.S.
PO Box 523,
010a, WA 98359
hoytj'eter@centurytel.net
360 874 05,62
Fax 360 874 0591
To: Jeanine Graf
1.2.1 5th Avenue N
121 5"" Ave. N
Edmonds, WA 98020
Re: Trike Shop
8505 240th Street SW
Plan. Review # 2006 -QEll' EECE # EDM 06-57(2)
The above referenced project is in the process of plan review for compliance with
Edmonds ordinances and applicable codes (Fin°°sklppression oitly). The following
comments, deficiencies/corrections must be addressed prior to completion of plans review
and subsequent issuance of permits.
Provide revised plans and calculations along with a written response to each of the items
listed below to facilitate a shorter back -check time.
SCOPE OF REVIEW
The scope of this review isfior 1,7re Supprevvion requirements qfthis project.
All features were checked only to the extent allowed by the submittals provided. All
portions of this project are assumed to meet or will meet other departmental requirements,
conditions and concerns before permit approval.
Fire Sunvression Comments
General
Page 2 of 2
EECE#: EDM 06-57(2)
Trike Shop
1. Modify the calculation on Pipe 8 to reflect 6 feet of pipe instead of 4 feet of pipe.
2. Is there a gate valve or a ball valve where the underground line connects to the city
line? If so, it needs to be added to the calculations. Usually there is a valve at that
location.
3. There is a concern with having two backflow prevention devices. They require
maintenance and annual testing. Also, should one of these devices fail (twice the
opportunity for this to happen) it will affect the flow of the sprinkler system. It seems
only logical to remove the device from the interior of the building.
Additional corrections may be required following receipt of corrections and
additional information as requested.
Your plans are being reviewed concurrently with the Building Department, Fire
Department, Zoning Department and Public Works Engineering. Changes,
clarifications or additional corrections may be required subsequent to the Building
Department plan review when comments are received from the other concerned
departments.
Should you have any inquiries regarding this letter, please contact Hoyt Jeter at
(360) 8740562 between 8:00 a.m. and 5:00 p.m.
0
Hoyt Jeter, P.E.
President
CLIENT:
E,a.'finonds, Bufld4ig Department
Ul 5th Avenue N
Ecrimoinds, VVA 98020
Attn: Jeannine Gmf, C.B.0,
Eagle Eye Consulting Engineers P.S.
PO BOX 523
Olall�a WA 98369
(360) 874-0562
Project Name: Triike Stop
E E C E Project # EDM 06-57
Client Reference Number : 2006-0578
'10/20/06 1l17/08
For valuation calculation purposes the following classffications for construction type and building use were utilized
Number of stories = 2 CM=
Occupancy (Use) / Constr. Type
T =Tz W M64
Main Floor
Upper Floor
Garaae
Deck
Im
Covered Patio
1 CM = 1
$ Per Square Foot
$92.40 X
$92.40 X
$92.40 x
$24,$0 x
$0.00 x
$0.00 x
Q
Gross Area
Building Valuation
$0.00
$0.00
$0.00
$0.00
$0.00
Ell
$0,00
$0.00
STATED CALCULATED DISCREPANCY
IF MORE THAN 10%
VALUATION: $0.00
Total Project Valuation, = $0.00 $0.00 #DlV/01
DFI: $ 23.50 $ 23,50
BUILDING PERMIT FEE! $23.50 $ 23.50
PLANCHECK FEE: $15.28 $ 1528
Eagle Eye Consulting Engineering Fees: (Box Checked are Fees Used for This Project)
S only
Eagle Eye consulting Frigineers
Fee (single family):
Eagle Eye Consulting Engineers
FEE (A arul Li Already Wiled $340
Eagle Eye Consulting Engineers Billed 4 hours first review 4
FEE (A ar S): hour for second review
Eagle Eye Consulting Engineers
Hourly Fee at $85/hour:F]Hours 78 $680,00
Notes
Single famli�ly 45%