Loading...
BLD20060845 Old Mill Town Rev 7.doc MEMORANDUM Date:January 2, 2008 To:Development Services Lead Theresa Umbaugh From:John Westfall, Fire Marshal (425) 771-0213 Subject:BLD20060845 Old Milltown Phase 1 Revision 7 th 201 5 Avenue S. The Fire Department provides the following comments and corrections in accordance with the 2003 International Fire Code and Edmonds Community Development Code: 1. Cloud your revisions. 2. Sheets A1.0.4, A2.0, & A2.01 Update revised OCCUPANCY INFO and new calculations from sheet A1.0 A 3. Fire protection vault is not allowed where designed-see Engineering comments. Please assure all sheets including A1.0.4, A2.0, A2.0.1, F2.0, A2.7, A4.0, C3 and Fire Connection permit are revised to show DCDA relocation information. 4. Sheets A1.0.4, A2.0, A2.0.1, F2.0, and A2.7 Exterior RETAIL doors (25) must open towards the direction of egress: outside. Revise door-swing. 5. Sheets A1.0 C and A.2.0.1 Provide approved “KEEP (CORRIDOR) CLEAR” signage throughout exit corridor and on OPENING SCHEDULE NOTES for doors 22, 49-54, and 60. 6. Sheet A.2.0.1 Callout FD lockbox symbol in vicinity of match line F.0/1.0. 7. Sheet A1.0.2 & A1.0.3, and C2 Assure 20’ clear apparatus width to a height of 13’ 6” adjacent to building for FIRE LANE purposes. 8. Sheet A1.0.2 & A1.0.3, and C2 Stripe and paint “FIRE LANE – NO PARKING” east of NEW CONC. CURB between parking and alley. City of Edmonds Office of Fire Marshal   9. Sheet A1.0 C Doors 34 and 43: delete “Door to remain open…” signs. The only hardware provided shall be panic hardware. Cc: Mr. Ralph Allen, AIA rwallen@bridgepm.net , fax 206-783-2037 Engineering Program Manager Jeanie McConnell Assistant Building Official Ann Bullis 2