BLD20061176 Summe Medical 7614 195 TI.doc
MEMORANDUM
Date:November 1, 2006
Development Services Lead Marie Harrison
To:
From:Fire Marshal John J. Westfall 425.771.0213
th
Subject:BLD20061176 Summe Medical TI 7614 194 St SW
The following project has been evaluated under the 2003 International Codes and
Edmonds Community Development Codes. Please resubmit with the following
corrections:
1. Code information: Note: “Non-sprinklered”.
2. Provide complete building calculations and summarize adjoining occupancy types.
ndst
Indicate tenant improvement on 2 floor with no work on 1 floor. Show common
building systems that will affect other units, call out separations, barriers required to
be maintained.
st
3. Suite numbering should indicate 2nd floor (west) entry vs. 1 floor (east) entry vs “A”
and “B”. City files show “201”, “202”, “203” from previous tenants.
4. Identify any hazardous lab materials, compressed gas, oxidizers, their quantities, or
3
absence of same. Portable oxidizer storage in cylinders is limited to 504 ft. Storage
in the building over this amount will require one-hour interior or exterior room
construction.
5. FD has record of existing building fixed medical gas system-will this system be
utilized, modified, removed, or be unremarkable due to separate ownership?
Cc: Mr. Anders Raman, TSE Architecture, fax 425.481.6371
Assistant Building Official Ann Bullis
City of Edmonds Fire Marshal