BLD20061195 Edm Prof Ctr 7315 212 St SW rev.doc
MEMORANDUM
Date:March 13, 2007
Development Services Lead Theresa Umbaugh
To:
From:Fire Marshal John J. Westfall 425.771.0213
th
Subject:BLD20061195-Edmonds Professional Center 7315 212 St SW.
Fire Comments Rev 2
The following plans resubmittal (dtd 2/9/07) has been evaluated under the 2003
International and Edmonds Community Development Codes. Additional
accommodations may be required as additional information is provided. Existing
structure is fully fire sprinklered & automatic fire alarmed.
1. OK
2. OK-sprinkler design will be extended upon existing system.
3. N/A
4. OK
5. OK
6. OK
7. Relocate Fire Department key box to permanent (south) main entrance. Notes A1.3
& A1.4. installed at the NE entry. Relocate box. Coordinate with Fire Department
at 425.775.7720
8. Required (deferred) permits/submittals include:
8.1. Fire Sprinkler System Permit
8.2. Fire Alarm Permit
8.3. Fire Protection Footprint.
9. Callout Fire Alarm Permit. Automatic Fire alarm system is required for the purposes
of sprinkler system monitoring, egress path detection integrity, auto-fire door
activation, local alarm audible/visual notification and exterior audibility. IFC 903.4.2
10. Add detail for Fire Hydrant: COE standard detail E7.1
(http://www.ci.edmonds.wa.us/CityDepartments/EngrDept/Edmonds-Std-
Details/CityOfEdmondsStandardDetails.pdf)
City of Edmonds Fire Marshal
11. Fire hydrant location shall be identified by the installation of approved blue
pavement reflective markers in the center of drive aisle perpendicular to the hydrant
location. IFC 508.5.4
12. OK
13. OK.
14. Sheet A3.2 (south elevation) add note: New and existing buildings shall have
approved address numbers, building numbers or approved building identification
placed in a position that is plainly legible and visible from the street or road fronting
the property. These numbers shall contrast with their background and visible from
public way. ECDC 19.75.005
15. OK
16. OK
17. OK
18. Sheet A2.2 automatic fire-rated assemblies including the rated overhead doors
between S2 and B occupancies shall be controlled by the building fire detection
system. Doors are 33’ and 9.5’ in length. (Building comment #14 dtd 12/11/06).
19. OK
20. Sheet A2.5 Note: Maintain fire alarm visibility & automatic fire protection in
conference spaces 1478 & 1477.
21. Sheet A2.5 Callout and post individual and aggregate occupant loads for
Conference spaces 1478 & 1477.
22. OK
23. See #18.
24. Will standby or emergency power be provided? If so, specify source, callout
location, detail fuel storage, and identify power requirments. Provide a list of
equipment connected to emergency power. The list should include, exhaust
ventilation, hazardous materials alarm, treatment systems, toxic gas detection, and
other required safety devices.
25. Provide hazardous materials and flammables inventory for all new areas and areas
with new tenants.
26. Sheet M1.0 General Note: Separate sprinkler and fire connection/supply permits
are required.
27. OK
28. OK
29. Sheet E3.01 Add note: “Fire Alarm information notional only. See Fire Alarm plans
for approved alarm installation requirements”
30. Sheet E3.01 Add note: “Fire Alarm accessibility upgrades are required throughout
and in existing building areas”
Cc: Architect Jackm@salmon-bay.com
Facility Planner johnc@salmon-bay.com
Assistant Building Official Ann Bullis
Engineering Program Manager Lyle Chrisman
Salmon Bay Design Group fax 206.783.6885