BLD20061331 NA CPA 8319 238.doc
MEMORANDUM
Date:January 11, 2007
Development Services Lead Theresa Umbaugh
To:
From:Fire Marshal John J. Westfall 425.771.0213
th
Subject:BLD20061331 Na CPA 8319 238 St SW
The following pre-application has been evaluated under the 2003 International Codes
and Edmonds Community Development Code.
1. A2.1 Provide a portable UL listed fire extinguisher minimum rated 2A:10B:C in each
hallway upon both levels.
2. A2.2 Provide emergency illumination in exitways if 2 required exits are intended
(see Building Dept Review comment #6b Ann Bullis 1/8/07)
3. A2.2 Delete (residential) smoke alarms. Provide, if desired, voluntary commercial
fire alarm system with smoke/heat detectors in accordance with Fire Alarm Code. A
fire alarm permit will be required for your system.
4. A3.1 Post building address in Arabic numerals or alphabet letters. Numbers shall be
legible from public way, at least 4 inches high with a ½ inch min. stroke width on a
contrasting background.
Cc: Mr. Kim, Kim_primary@comcast.net
Assistant Building Official Ann Bullis
City of Edmonds Fire Marshal