BLD20061331 NA CPA 8319 238.doc MEMORANDUM Date:January 11, 2007 Development Services Lead Theresa Umbaugh To: From:Fire Marshal John J. Westfall 425.771.0213 th Subject:BLD20061331 Na CPA 8319 238 St SW The following pre-application has been evaluated under the 2003 International Codes and Edmonds Community Development Code. 1. A2.1 Provide a portable UL listed fire extinguisher minimum rated 2A:10B:C in each hallway upon both levels. 2. A2.2 Provide emergency illumination in exitways if 2 required exits are intended (see Building Dept Review comment #6b Ann Bullis 1/8/07) 3. A2.2 Delete (residential) smoke alarms. Provide, if desired, voluntary commercial fire alarm system with smoke/heat detectors in accordance with Fire Alarm Code. A fire alarm permit will be required for your system. 4. A3.1 Post building address in Arabic numerals or alphabet letters. Numbers shall be legible from public way, at least 4 inches high with a ½ inch min. stroke width on a contrasting background. Cc: Mr. Kim, Kim_primary@comcast.net Assistant Building Official Ann Bullis City of Edmonds Fire Marshal  