BLD20061378 KUPC FA 8505 240 St.doc
MEMORANDUM
Date:January 18, 2007
Development Services Lead Marie Harrison
To:
From:Fire Marshal John J. Westfall 425.771.0213
Subject:BLD20061378 KUPC FA 8505 240 St SW
The following project has been evaluated under the Edmonds Community Development
Code, 2003 International Codes and NFPA 72. Resubmittal is required.
1. Use prescriptive design for required detection of exit corridors, halls, gathering,
lobbies, stairs, and along common paths of egress for each floor. Smoke
detectors shall be properly spaced at 30’ throughout these egress areas.
2. Add smoke detector at top of lobby stair enclosure on main floor.
3. Smoke detection not required in CONFERENCE HALL.
4. Relocate voice evac panel to main floor LOBBY next to annunciator.
5. Add module for commercial cooking system tie-in to fire alarm system
KITCHEN.
6. All manual pulls at LOBBY and CORRIDOR exits on lower floor.
7. Add horn-strobes in CRY & MEDIA rooms on upper floor.
8. Provide notification at LOBBY stair landing (lower floor).
9. Provide notification throughout lower floor LOBBY and CORRIDOR.
10. Provide notification to each UNOCCUPIED/unfinished space, access
dependent.
11. Resubmit battery calculations.
Cc: Matt Kellogg, Washington Alarm, fax 206-322-7214
Asst. Building Official Ann Bullis
City of Edmonds Fire Marshal