Loading...
BLD20070014 Gregory FA.doc MEMORANDUM Date:February 7, 2007 Development Services Lead Marie Harrison To: From:Fire Marshal John J. Westfall 425.771.0213 th Subject:BLD20070014 Gregory FA 505 5 Ave S The following pre-application has been evaluated under the 2003 International Codes and Edmonds Community Development Code. Please resubmit with corrections. 1. Sheet F4/6 Interconnect ¾ hr FR Blaze Guard fire shutters at building entry to building fire alarm system (IFC 907.10). Provide interconnected shutter-functioning detector(s) as required in accordance with NFPA 80 and manufacturer’s instructions. 2. Sheet F2/6 & F3/6 - Notate tamper connections to PIV, DCDA (2 valves) and sprinkler control valves on plans. 3. Sheets F3/6 through F6/6 – AOR (two-way communications) equipment proposals within scope of FA contract should be added to JOB NOTES and design-specified on fire alarm plans. Provide cut sheets for AOR-related equipment. Add missing AORs at Exit Stair 1. Provide addressable refuge-end notification at head-end. 4. Sheet F3/6 Add hornstrobe located approx. parking space 60 and visible throughout ramp area. 5. Sheet F4/6 Strobe-only notification for restrooms. 6. Sheets F4/6 through F6/6 – Redesign corridor smoke detector spacing to 30’ or show manufacturer’s suggested design spacing. NFPA 5.7.3.2.3.1 7. Sheet F4/6 Anticipate power requirements for future notification requirements throughout tenant improvement areas. 8. Sheet F4/6 through F6/6 Add smoke detection and notification appliances in egress components: STAIR1 & STAIR 2. th 9. Sheet F5/6 Relocate exterior horn/strobe to 5 Avenue entry wall area. 10. Sheet F1/6 Update riser diagram and battery calculations with corrected design actions. Cc: Mr. Luke Gallison, Gallison Systems lgallison@msn.com Assistant Building Official Ann Bullis City of Edmonds Fire Marshal  