BLD20070060 Clearwire ECA Collocate.doc MEMORANDUM Date:February 6, 2007 Development Services Lead Marie Harrison To: From:Fire Marshal John J. Westfall 425.771.0213 th Subject:BLD20070060 Clearwire ECA Collocate 410 4 Ave N. The following project has been evaluated under the 2003 International Codes and Edmonds Community Development Code. 1. Provide valve-regulated lead acid (VRLA) or lead acid battery manufacturer cut sheet and Material Safety Data Sheet (MSDS) in weatherproof container posted next to equipment cabinet. 2. Callout number of batteries used for backup or provide volume of battery electrolyte. 3. Identify sulfuric acid electrolyte hazard with NFPA 704 diamond posted on gate. NFPA label is blue-2, red-0, yellow-1, white-n/a. 0 2 1 Post weatherproof diamond no less than 8” square on approach to equipment exterior. 4. Seal penetrations in fire walls and partitions where core-drilling, power or signal wiring move through fire-rated assemblies. See IBC 712. Cc: Mr. Todd Walton, Clearwire, fax 361-9606 Asst. Building Official Ann Bullis City of Edmonds Fire Marshal  