Loading...
BLD20070200-1 Westgate Arms FA 9804-8 Edmonds Way.doc MEMORANDUM Date:March 15, 2007 To:Development Services Lead Theresa Umbaugh From:John Westfall, Fire Marshal (425) 771-0213 Subject:BLD20070200-1 Westgate Arms Condos FIRE ALARM 9804-8 Edmonds Wy The Fire Department provides the following comments and corrections in accordance with the 2003 International Fire Code and Edmonds Community Development Code: 1. Provide manual and automatic fire alarm system throughout for non-sprinklered structure installed iaw IFC and NFPA 72 & remotely monitored. 2. Add note: dwelling and common area audibility must meet requirements of IFC 907.10.2 (typical). 3. Re-label Building A as 9504 and Building B as 9508 throughout. 4. Sheets 3 & 3A add note: See building plans for dwelling smoke (“Fire Alarm”) placement (typical). 5. Sheet 4 add smoke & redesign RECREATION & LOUNGE for proper detection coverage. 6. Sheet 4 add heats under stair storage areas. 7. Consider magnetic hold-opens for open/efficient pedestrian flow across fire-rated assemblies. 8. Update riser diagram and circuit configurations. Cc: Michael Trower; Catapult Development, mtrower@catapultdevelopment.com City of Edmonds Office of Fire Marshal  