Loading...
BLD20070218 La Chiquita 22921 #I Hwy99 Redlines.doc MEMORANDUM Date:May 16, 2007 Development Services Lead Marie Harrison To: From:Fire Marshal John J. Westfall 425.771.0213 Subject:BLD20070218 La Chiquita 22921 #I Hwy 99 Fire Dept corrections (dtd 3/14/07) have not been addressed by applicant. This project has been evaluated under the Edmonds Community Development Code, 2003 International Fire Code. Building has no fire alarm or fire sprinkler systems. OK 1. Call out existing suite numbers (I & H?) on existing floor plans. 2. Verify that food production will not include deep fat frying or other cooking that NO RESPONSE creates grease-laden vapors. Indicate this on plans. 3. Provide illuminated exit sign with battery backup at second exit (Building Dept. nd NO 2 EXIT RQRD per COE BLDG. note #2). NO RESPONSE 4. Provide means of egress illumination along exit paths. 5. Call out minimum rated 2A:10B:C rated portable fire extinguisher. NO RESPONSE NO RESPONSE- 6. Provide a furniture/shelving plan for new suite (#I?). BUSINESS LICENSE APPROVAL CONTINGENT UPON APPROVED FURNITURE/SHELVING PLAN. REDLINES/NOTES Fire has redlined plans with requirements. The following are added to plans: Class II hood installation. Commercial food production shall not include grilling,  deep fat frying or any cooking that creates grease-laden vapors. Provide means of egress illumination along exit paths where shown (EM LTS).  Provide minimum 2A:10B:C rated portable fire extinguisher where shown (FE).  th Cc: Ms Tina Gutierrez, 3130 NE 20 Place, Renton, WA 98056 City of Edmonds Fire Marshal   Asst. Building Official Ann Bullis