BLD20070302 Sun DDS 21911 76 #203 A.doc
MEMORANDUM
Date:April 26, 2007
Development Services Lead Marie Harrison
To:
From:Fire Marshal John J. Westfall 425.771.0213
th
Subject:BLD20070302 Dr. Ben Sun 21911 76 Ave W #203 Corrections
The following project has been evaluated under the Edmonds Community Development
Code, 2003 International Fire Code.
1. Permits required:
a. Building fire alarm notification plan requires separate permit.
b. Occupancy permit is required for storage of oxidizers exceeding MAQ of
3
504 ft. $30 annual permit fee is required to Edmonds Fire Dept. Your
permit will be issued upon final project approval.
OK: CORRECTED AND REDLINED.
2. Building sprinkler system is designed is to light hazard protection. Identify and
nd
resolve any required upgrades for 2 floor gas storage (see Endodontics #208).
~AWAITING RESOLUTION.
3. NOTE:
Per IFC, the Max Allowable Quantity (MAQ) for medical gases is 6,000 CF
stored per control area when the building is sprinklered throughout with
NFPA 13 system and the area is approved exhausted enclosure.
OK: CORRECTED AND REDLINED
4. Locations containing cylinders containing only oxygen or medical air shall have
their door(s) labeled as follows:
CAUTION
Medical Gases
NO Smoking or Open Flame
OK: REDLINED
5. Install emergency lights in OP and in RECEPTION/WAITING areas.
OK: CORRECTED
Cc: Ms. Susan Yerkes, saydesign@wavecable.com
Mastgech LLC, mastgech@yahoo.com
City of Edmonds Fire Marshal
Asst. Building Official Ann Bullis