Loading...
BLD20070302 Sun DDS 21911 76 #203.doc MEMORANDUM Date:April 12, 2007 Development Services Lead Marie Harrison To: From:Fire Marshal John J. Westfall 425.771.0213 th Subject:BLD20070302 Dr. Ben Sun 21911 76 Ave W #203 The following project has been evaluated under the Edmonds Community Development Code, 2003 International Fire Code. 1. Permits required: a. Building fire alarm notification plan requires separate permit. b. Occupancy permit is required for storage of oxidizers exceeding MAQ of 3 504 ft. $30 annual permit fee is required to Edmonds Fire Dept. Your permit will be issued upon final project approval. 2. Building sprinkler system is designed is to light hazard protection. Identify and nd resolve any required upgrades for 2 floor gas storage (see Endodontics #208). 3. NOTE: Per IFC, the Max Allowable Quantity (MAQ) for medical gases is 6,000 CF stored per control area when the building is sprinklered throughout with NFPA 13 system and the area is approved exhausted enclosure. 4. Locations containing cylinders containing only oxygen or medical air shall have their door(s) labeled as follows: CAUTION Medical Gases NO Smoking or Open Flame 5. Install emergency lights in OP and in RECEPTION/WAITING areas. Cc: Ms. Susan Yerkes, saydesign@wavecable.com Mastgech LLC, mastgech@yahoo.com Asst. Building Official Ann Bullis City of Edmonds Fire Marshal  