BLD20070302 Sun DDS response.txt
BLD20070302 Sun DDS response
From: DENNIS SKINNER \[fpsds@qwest.net\]
Sent: Wednesday, May 16, 2007 4:39 PM
To: Westfall, John
Subject: Endodontics Northwest
Subject: Endodontics Northwest
21911 76th Ave W Ste# 208
Edmonds, WA
Application #: BKD20070520
The above dentist office is classified as a light hazard occupancy. The fire
sprinklers are spaced at a maximum of 225 sq. ft. per sprinkler head & discharges at
a minimum of .10 gallons per minute per sq ft.of floor area. The gas closet in this
space is 5'-0" x 1'-6", for the total of 7.5 sq ft. This small room has one quick
response sprinkler head that will discharge a minimum of 22.5 gallons per minute.
This equates to a density of 3.0 gallons per minute per sq ft in this room. This
density is well above any extra hazard or storage density in NFPA #13. If you have
any questions please give me a call.
Dennis Skinner
Page 1