BLD20070302 Sun DDS response.txt BLD20070302 Sun DDS response From: DENNIS SKINNER \[fpsds@qwest.net\] Sent: Wednesday, May 16, 2007 4:39 PM To: Westfall, John Subject: Endodontics Northwest Subject: Endodontics Northwest 21911 76th Ave W Ste# 208 Edmonds, WA Application #: BKD20070520 The above dentist office is classified as a light hazard occupancy. The fire sprinklers are spaced at a maximum of 225 sq. ft. per sprinkler head & discharges at a minimum of .10 gallons per minute per sq ft.of floor area. The gas closet in this space is 5'-0" x 1'-6", for the total of 7.5 sq ft. This small room has one quick response sprinkler head that will discharge a minimum of 22.5 gallons per minute. This equates to a density of 3.0 gallons per minute per sq ft in this room. This density is well above any extra hazard or storage density in NFPA #13. If you have any questions please give me a call. Dennis Skinner Page 1