Loading...
BLD20070382 21827 76th Reichler 3.doc MEMORANDUM Date:December 10, 2007 To:Development Services Lead Marie Harrison From:John Westfall, Fire Marshal, 425-771-0213 th Subject:BLD200700382 ReichlerOffice Bldg REVISION 21827 76 Ave W The Fire Department provides the following comments and corrections in accordance with the 2006 International Fire Code and Edmonds Community Development Code: 1. Sheet A1.0 FIRE CONNECTION PERMIT Add wording: “…copies of plans showing all valves, vault location, Double Check Detector Assembly, post…” 2. Sheet 2.0 Callout EXERCISE ROOM referred to in OCCUPANT LOADS from A1.0. 3. Sheet A2.0 Show cardinal direction arrow for plans. 4. Sheet A2.0 Provide EXIT signage a. PARKING: EXIT passageway at DOOR 006 b. MAIN: Tenant #2 c. MAIN: Tenant-side DOOR 106 5. Sheet A2.0 Provide EMERGENCY ILLUMINATION a. MAIN: Tenant space #2 b. MAIN: Elevator lobby c. UPPER: Tenant #3 d. UPPER: Tenant #4 e. UPPER: Elevator lobby f. UPPER: (both) Stair wells g. UPPER: Waiting area 6. Sheet A2.0 Delete EXIT sign on tenant #2 side of DOOR 102 7. Sheet A2.0 Provided minimum 2A:10B:C rated portable fire extinguisher @ DOOR 106. 8. Sheet A4.0 Door 006 cannot be HARDWARE set A: key-lock configured for egress side. 9. Note: Fire alarm devices are notional-see separate fire alarm permit for actual device locations. City of Edmonds Office of Fire Marshal   Cc: Mr. Ralph Allen rwallen@gracearchitectspllc.com Assistant Building Official Ann Bullis 2