MEMORANDUM
Date:February 26, 2008
To:Development Services Lead Marie Harrison
From:John Westfall, Fire Marshal, 425-771-0213
Subject:BLD200700382 ReichlerOffice Bldg REVISION 4
th
21827 76 Ave W
The Fire Department provides the following comments and corrections in accordance with the 2006
International Fire Code and Edmonds Community Development Code:
1. OK
2. Sheet A1.0 Remove EXERCISE ROOM from OCCUPANT LOADS calculation.
3. OK
4. Sheet A2.0 Provide EMERGENCY ILLUMINATION
a. PARKING LEVEL: Elevator lobby
5. OK
6. OK
7. OK
8. OK
9. Sheet A1.0 FIRE CONNECTION permit is separate not deferred. Please submit as soon as
possible.
10. Sheet A2.0 Add NOTE: Automatic-closing doors controlled by spot or area smoke detectors tied
to building fire alarm system.
11. Sheet A4.0 Add NOTE: Overhead coiling door #201 and other automatic closing assemblies will
be activated by a spot or area smoke detector tied to building fire alarm system.
12. Sheet A4.0 DOOR SCHEDULE: Only door 101 is considered primary entrance for purposes of
“REMAINING UNLOCKED DURING BUSINESS HOURS” and HARDWARE set A. Doors 03
and 05 are not primary entrances, HARDWARE set E is suggested.