BLD20070640-5 Valhalla Townhomes Edm Wy RESUB.doc
MEMORANDUM
Date:November 29, 2007
To:Development Services Lead Marie Harrison
From:John Westfall, Fire Marshal (425) 771-0213
Subject:BLD20070640, BLD20070641, BLD20070642, BLD20070643,
BLD20070644, BLD20070645 RESUB
nd
232 Street Townhomes 23004-23014 Edmonds Wy
The Fire Department provides the following comments and corrections in accordance with the 2003
International Fire Code and Edmonds Community Development Code:
All permits Sheet A0
1. SEPARATE PERMITS
a. Delete reference to FIRE SPRINKLER. Sprinkler is not required except for 5 or more
townhomes.
Exceptions:
i Voluntary NFPA 13R sprinkler allowed with penetrations meeting IRC R317
ii Voluntary NFPA 13D sprinkler allowed for each dwelling with no penetrations.
Iii Voluntary sprinkler system requires Fire Connection permit.
2. SITE PLAN
a. Draw clear approved turnaround where DRIVE AISLE takes turn so that BLDG A
does not exceed 150’ vehicular access for firefighting purposes.
b. Show fire lane from north DRIVE AISLE entry to south DRIVE AISLE egress. Fire
lane shall be striped with 4” yellow perimeter striping and identified with words “FIRE
LANE – NO PARKING”. Letters shall be 12” high with 2” stroke spaced 50 lineal feet
on alternating insides of lane.
3. BUILDING CODE
a. Clarify IRC construction and delete IBC references.
b. Correct OCCUPANCY GROUPS are R3/U.
c. Building is not required to be “FULLY SPRINKLERED”. Remove from table and
recalculate.
i. Voluntary sprinkler systems: Automatic sprinkler system increase may be
taken for approved NFPA 13 (903.3.1.1) or NFPA 13R (903.3.1.2) systems.
NFPA 13D (903.1.1.3) systems for dwellings do not meet minimum
requirements for height or area increases IBC 504.2
4. ZONING CODE
City of Edmonds Office of Fire Marshal
a. Correct OCCUPANCIES are R3 / U.
All permits Sheet A0.1
5. CONTRACTOR COORDINATION NOTES
a. Delete 2.C and 2.D or re-evaluate for voluntary sprinkler system(s).
b. Add NOTE: “FIRE PREVENTION PROGRAM SUPERINTENDENT POC IS (add
name and telephone # here) AND 24 HOUR TELEPHONE CONTACT FOR
EMERGENCY PURPOSES. FP PROGRAM SUPERINTENDENT SHALL HAVE
AUTHORITY TO ENFORCE FIRE SAFETY PROVISIONS.”
6. DIAGRAMMATIC
a. Correct “R3” vs. “R2”
BLD20070640 Building A 23004
7. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units A-2 and A-3.
b. Sheet A3.1 Show FE in south elevation
8. Sheet A3.1 Add building address signage on north elevation.
9. Sheets A2.2 & A2.3 Add hardwired, interconnected smoke alarms with battery backup at each
dwelling level, inside and outside sleeping rooms. OK
BLD20070641 Building B 23006
10. Sheet A2.1-B & A3.1-B Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units B-1 and B-2.
b. Sheet A3.1 Show FE in south elevation
11. Sheet A3.1 Add building address signage on north elevation.
12. Sheets A2.1-B & A2.2-B Add hardwired, interconnected smoke alarms with battery backup at
each dwelling level, inside and outside sleeping rooms.
BLD20070641 Building C 23008
13. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units C-2 and C-3.
b. Sheet A3.1 Show FE in south elevation
14. Sheet A3.1 Add building address signage on north elevation.
15. Sheets A2.2 & A2.3-C Add hardwired, interconnected smoke alarms with battery backup at
each dwelling level, inside and outside sleeping rooms.
2
BLD20070641 Building D 23010
16. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units D-2 and D-3.
b. Sheet A3.1 Show FE in south elevation
17. Sheet A3.1 Add building address signage on north elevation.
18. Sheets A2.2 & A2.3 Add hardwired, interconnected smoke alarms with battery backup at each
dwelling level, inside and outside sleeping rooms.
BLD20070641 Building E 23012
19. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units E-2 and E-3.
b. Sheet A3.1 Show FE in north elevation
20. Sheet A3.1 Add building address signage on north elevation.
21. Sheets A2.2 & A2.3 Add hardwired, interconnected smoke alarms with battery backup at each
dwelling level, inside and outside sleeping rooms.
BLD20070641 Building F 23014
22. Sheet A3.1 Correct cardinal directions to elevations.
23. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units F-1 and F-2.
b. Sheet A3.1 Show FE in north elevation
24. Sheet A3.1 Add building address signage on north elevation.
25. Sheets A2.2 & A2.3 Add hardwired, interconnected smoke alarms with battery backup at each
dwelling level, inside and outside sleeping rooms.
Cc: Mr. Tony Shapiro, A.D. Shapiro Architects tonys@adshapiro.com
Mr. James Abbott, SGA Corporation, jabbott@sgacorp.com
Engineering Program Technician Jeanie McConnell
Assistant Building Official Ann Bullis