BLD20070640-5 Valhalla Townhomes Edm Wy.doc
MEMORANDUM
Date:August 16, 2007
To:Development Services Lead Marie Harrison
From:John Westfall, Fire Marshal (425) 771-0213
Subject:BLD20070640, BLD20070641, BLD20070642, BLD20070643,
BLD20070644, BLD20070645
nd
232 Street Townhomes 23004-23014 Edmonds Wy
The Fire Department provides the following comments and corrections in accordance with the 2003
International Fire Code and Edmonds Community Development Code:
All permits:
1. GENERAL NOTES ALL permits:
a. Establish site drive aisle with two access points and maintain vehicle access through
construction work for firefighting purposes.
b. Maintain fire hydrant access through demo and construction work.
c. Identify Fire Prevention Program Superintendent POC and 24 hour telephone
contact for emergency purposes. Superintendent shall have authority to enforce fire
safety provisions.
IFC Sections 1408, 1410, 1412
2. Sheet A0.1 ALL permits:
a. 2A Correct “(NFPA 72A 72)”.
b. 2C. Correct “NFPA 13R “.
c. 2D. Add: “Fire Connection Permit required to be submitted with Civils, not deferred,”
d. 2E. Add: “Fire Safety and Evacuation Guide
Provide a guide which describes the location, function and use of fire
protection equipment and appliances accessible to residents, including fire
alarm systems, smoke alarms, and portable fire extinguishers in R2
apartments and condominiums .”
Email westfall@ci.edmonds.wa.us for example IFC 408.9
e. 3E. Correct “ City of Seattle Olympic View Water Sewer District”.
f. Add note: Provide Fire Department lockbox. Coordinate with Fire Department for a
“Lockbox Authorization Letter” and instructions to obtain and install lockbox outside
the sprinkler rooms on your site. 425.775.7720
3. Sheet A1.1 ALL permits-details 12 & 17 Fire sprinkler closet
a. Add note: Min 40 degrees F.
City of Edmonds Office of Fire Marshal
b. Add note: Collocate FACP w/ fire risers
BLD20070640 Building A 23004
4. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units A-2 and A-3.
b. Sheet A3.1 Show FE in south elevation
5. Sheet A3.1 Add building address signage on north elevation.
6. Sheets A2.2 & A2.3 Add hardwired, interconnected smoke alarms with battery backup at each
dwelling level, inside and outside sleeping rooms.
BLD20070641 Building B 23006
7. Sheet A2.1-B & A3.1-B Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units B-1 and B-2.
b. Sheet A3.1 Show FE in south elevation
8. Sheet A3.1 Add building address signage on north elevation.
9. Sheets A2.1-B & A2.2-B Add hardwired, interconnected smoke alarms with battery backup at
each dwelling level, inside and outside sleeping rooms.
BLD20070641 Building C 23008
10. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units C-2 and C-3.
b. Sheet A3.1 Show FE in south elevation
11. Sheet A3.1 Add building address signage on north elevation.
12. Sheets A2.2 & A2.3-C Add hardwired, interconnected smoke alarms with battery backup at
each dwelling level, inside and outside sleeping rooms.
BLD20070641 Building D 23010
13. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units D-2 and D-3.
b. Sheet A3.1 Show FE in south elevation
14. Sheet A3.1 Add building address signage on north elevation.
15. Sheets A2.2 & A2.3 Add hardwired, interconnected smoke alarms with battery backup at each
dwelling level, inside and outside sleeping rooms.
2
BLD20070641 Building E 23012
16. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units E-2 and E-3.
b. Sheet A3.1 Show FE in north elevation
17. Sheet A3.1 Add building address signage on north elevation.
18. Sheets A2.2 & A2.3 Add hardwired, interconnected smoke alarms with battery backup at each
dwelling level, inside and outside sleeping rooms.
BLD20070641 Building F 23014
19. Sheet A3.1 Correct cardinal directions to elevations.
20. Sheet A2.1 & A3.1 Garage plan
a. Sheet A2.1 Install min. rated 2A:10B:C portable fire extinguisher (FE) between garage
entries for units F-1 and F-2.
b. Sheet A3.1 Show FE in north elevation
21. Sheet A3.1 Add building address signage on north elevation.
22. Sheets A2.2 & A2.3 Add hardwired, interconnected smoke alarms with battery backup at each
dwelling level, inside and outside sleeping rooms.
Cc: Mr. Tony Shapiro, A.D. Shapiro Architects tonys@adshapiro.com
Mr. James Abbott, SGA Corporation, jabbott@sgacorp.com
Engineering Program Technician Jeanie McConnell
Assistant Building Official Ann Bullis