MEMORANDUM
Date:September 18, 2007
To:Development Services Lead, Marie Harrison
From:John Westfall, Fire Marshal 425-771-0213
Subject:BLD20070686 Point Edwards Building #10 50 Pine Street
The Fire Department provides the following comments reviewed under 2003
International Codes and Edmonds Community Development Code.
1. SURFACE PARKING on south end should support the live loads of fire apparatus.
2. Standpipe design covers all levels. At level L1 standpipe inside floor exit.
3. Sheet A0.0 DEFERRED SUBMITTALS
Add text: “4. FIRE SPRINKLER / STANDPIPE SYSTEM
4. Sheets A2.1, A2.2
“Maintain > 40 degrees F” in RISER ROOM.
5. Sheets A2.0-A2.9
Provide min. 2A:10B:C portable fire extinguishers at accessible locations at floor
exits, and every 75’ travel distance.
6. Sheets A2.0-A2.9
Provide exit signs and emergency illumination at junctions and turns in paths of
egress and every 100’ or listed view of sign, whichever is less.
7. Sheets A2.0-A2.9 GENERAL NOTES
Signage key is A8.3
8. Sheet A2.5
Provide additional exit signage in parking area providing direction for egress.
9. Sheet A6.07, A6.11, A6.24, A6.25
Add smoke alarms in unit B7, E1, E2, TH-1L, TH-1U bedrooms.
City of Edmonds Office of Fire Marshal
10. Sheets A6.14 & A6.21
Move smoke alarms to open area of ceiling.
11. Sheets A6.16 & A6.18
nd
Move 2 G. Bedroom smoke alarm to hall.
12. Sheet A6.19
Delete bathroom smoke alarm.
Cc: Valerie Sargent, Weber + Thompson Architects, fax 206 749-5005
Bruce Moe, Point Edwards LLC, fax 206 770-7761
Asst. BO Ann Bullis