Loading...
BLD20070686 Point Edwards 10.doc MEMORANDUM Date:September 18, 2007 To:Development Services Lead, Marie Harrison From:John Westfall, Fire Marshal 425-771-0213 Subject:BLD20070686 Point Edwards Building #10 50 Pine Street The Fire Department provides the following comments reviewed under 2003 International Codes and Edmonds Community Development Code. 1. SURFACE PARKING on south end should support the live loads of fire apparatus. 2. Standpipe design covers all levels. At level L1 standpipe inside floor exit. 3. Sheet A0.0 DEFERRED SUBMITTALS Add text: “4. FIRE SPRINKLER / STANDPIPE SYSTEM 4. Sheets A2.1, A2.2 “Maintain > 40 degrees F” in RISER ROOM. 5. Sheets A2.0-A2.9 Provide min. 2A:10B:C portable fire extinguishers at accessible locations at floor exits, and every 75’ travel distance. 6. Sheets A2.0-A2.9 Provide exit signs and emergency illumination at junctions and turns in paths of egress and every 100’ or listed view of sign, whichever is less. 7. Sheets A2.0-A2.9 GENERAL NOTES Signage key is A8.3 8. Sheet A2.5 Provide additional exit signage in parking area providing direction for egress. 9. Sheet A6.07, A6.11, A6.24, A6.25 Add smoke alarms in unit B7, E1, E2, TH-1L, TH-1U bedrooms. City of Edmonds Office of Fire Marshal   10. Sheets A6.14 & A6.21 Move smoke alarms to open area of ceiling. 11. Sheets A6.16 & A6.18 nd Move 2 G. Bedroom smoke alarm to hall. 12. Sheet A6.19 Delete bathroom smoke alarm. Cc: Valerie Sargent, Weber + Thompson Architects, fax 206 749-5005 Bruce Moe, Point Edwards LLC, fax 206 770-7761 Asst. BO Ann Bullis 2