bld20070884 - Pt Edwards Amenity 2.pdf
City of Edmonds
TH
121 5 AVENUE NORTH EDMONDS, WA 98020 (425) 771-0220 FAX(425) 771-0221
Website: www.ci.edmonds.wa.us
DEVELOPMENT SERVICES DEPARTMENT
Planning Building Engineering
Plan Review Corrections
Application : Date:
# bld20070884 December 5, 2007
Project Name/Address:
Pt Edwards Amenity 2
Contact Person/Address, Fax or E-mail:
Valerie Sargent / vsargent@weberthompson.com
Reviewer: Jeanie McConnellDivision:Engineering
During review of the above noted application, it was found that the following information, corrections, or
clarifications are needed. Please redline plans or submit three (3) sets of revised plans/documents with a
written response to each of the items below to Marie Harrison.
GENERAL
1.The retaining wall is being reviewed under a separate permit.
2.The pool is being reviewed under a separate permit.
3.In general, to provide clarity to the plans, please bold all items that pertain to individual plan sheets and gray
out others.
Sheet 4E TESC Plan
1.Provide reference to and include standard detail E1.3 Catch basin protection
Sheet 4F Fine Grading
1.Please revise plans to show all Loop Road improvements that are to be completed under this permit. The
plans currently only show a directional arrow up towards Pine Street.
2.As this is the grading plan, please revise the existing shoring wall/design by others along the SE property
line to show as bold line type as is shown on sheet 13 and 22.
Sheet 8 Details
1.The driveway approach standard detail shall be per City standard detail E2.26 or if a radius entrance is
preferred then the approach shall be per standard detail E2.27.1. Please revise plans accordingly and
specifically call out the width of the driveway approach required to accommodate both the ADA parking
stall and the fire lane.
DATE E-MAILED 12/5/07 PAGE 1 of 2
Sheet 13 - Road and Storm Drainage Plan
1.The geoblock sub-base shall be per manufacturers specs and/or requirements established by the engineer of
record. Please confirm that 6 crushed rock sub-base is acceptable. Compaction reports will be required
prior to placement of geoblock. Please also include detail of geoblock with this plan set.
2.The driveway approach standard detail as shown on sheet 8 of 30 shall be per City standard detail E2.26 or if
a radius entrance is preferred then the approach shall be per standard detail E2.27.1. Please revise plans
accordingly and specifically call out the width of the driveway approach required to accommodate both the
ADA parking stall and the fire lane
Sheet 22 Sewer and Water Plan
1. A 2 domestic water meter with RPBA is shown to be located within the lawn/geoblock fire lane. Please
relocate the water meter outside this driveable surface. A note has been added to the plans that states
relocate outside fire lane as necessary, but the plans actually need to show the revised location.
2.Please provide sewer invert elevation for the cleanout located to the NW of the fire lane. A minimum 18
separation should be provided between water and sewer and sufficient cover shall be provided over the pipe
for fire truck loads on a geoblock surface.
Please contact me at 425-771-0220 or by e-mail at mcconnell@ci.edmonds.wa.us if you have specific
questions regarding these plan corrections.
DATE E-MAILED 12/5/07 PAGE 2 of 2